Operating Position; Securing The Burner To The Boiler; Preparing The Boiler - Riello RS 100/M Instrucciones De Instalación, Uso Y Mantenimiento

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Installation
4
4.4

Operating position

The burner is designed to operate only in the positions
1, 2, 3 and 4.
Installation 1 is preferable, as it is the only one that al-
lows the maintenance operations as described in this
manual. Installations 2, 3 and 4 permit operation but
make maintenance and inspection of the combustion
head more difficult.
Any other position could compromise the correct opera-
tion of the appliance. Installation 5 is prohibited for
safety reasons.
4.5

Securing the burner to the boiler

Preparing the boiler

Boring the boiler plate
Make holes in the plate shutting off the combustion chamber, as illustrated in Fig. 10.
The position of the threaded holes can be marked using the thermal insulation
screen supplied with the burner.
mm
A
RS 100/M
185
Length of the blast tube
The length of the blast tube must be selected according to the indications pro-
vided by the manufacturer of the boiler, and in any case it must be greater
than the thickness of the boiler door complete with its refractory.
The available lengths L are those indicated in the table below.
Blast tube
short
RS 100/M
250 mm
For boilers with front flue passes 15) or flame
inversion chamber, a protection in refractory mate-
rial 13) must be inserted between the boiler fet-
tling 14) and the blast tube 12).
This protection must not compromise the extrac-
tion of the blast tube. See Fig. 11.
For boilers with a water-cooled frontal, a refractory
lining 13)-14) is not necessary unless expressly
requested by the boiler manufacturer.
20015724
B
C
275 - 325
M 12
long
385 mm
Fig. 11
1
2
11
10
1
2
5
D8688
12
GB
3
4
D7739
Fig. 10
15
15
6
5
Fig. 9
D455
14
13
12
9
8
3
7
4
3

Capítulos

Tabla de contenido
loading

Este manual también es adecuado para:

1117 t

Tabla de contenido