Group Name
Setup/Relay 1/Control
Setup/Relay 1/Control
Setup/Relay 1/Control
Setup/Relay 1/Control
Setup/Relay 1/Control
Setup/Relay 1/Control
Setup/Relay 1/Event
Setup/Relay 1/Event
Setup/Relay 1/Event
Setup/Relay 1/Event
Setup/Relay 1/Event
Setup/Relay 1/Event
Setup/Relay 1/Event
Setup/Relay 1/Timer
Setup/Relay 1/Timer
Setup/Relay 1/Timer
Setup/Relay 1/Timer
Setup/Relay 1/Timer
Setup/Relay 1/Timer
Setup/Relay 1/Status
Setup/Relay 2
Setup/Relay 2
Setup/Relay 2
Tabla A-8 Controller ModBUS Registers (continuado)
Tag Name
Register # Data Type
Phase
40067
Deadband
40068
Overfeed
40070
Timer
On Delay
40071
Off Delay
40072
Reset
Overfeed
40073
Timer
Setpoint
40074
Phase
40076
Deadband
40077
On Max Time
40079
On Min Time
40080
Off Max Time
40081
Off Min Time
40082
Hold Type
40083
Sensor Select
40084
Hold Mode
40085
Duration Time
40086
Period Time
40087
Off Delay
40088
Level
40089
Source
40090
Sensor Select
40091
Measurement
40092
Select
Length
R/W
Unsigned
1
R/W
Integer
Float
2
R/W
Unsigned
1
R/W
Integer
Unsigned
1
R/W
Integer
Unsigned
1
R/W
Integer
Unsigned
1
R/W
Integer
Float
2
R/W
Unsigned
1
R/W
Integer
Float
2
R/W
Unsigned
1
R/W
Integer
Unsigned
1
R/W
Integer
Unsigned
1
R/W
Integer
Unsigned
1
R/W
Integer
Unsigned
1
R/W
Integer
Unsigned
1
R/W
Integer
Unsigned
1
R/W
Integer
Unsigned
1
R/W
Integer
Unsigned
1
R/W
Integer
Unsigned
1
R/W
Integer
Unsigned
1
R/W
Integer
Unsigned
1
R/W
Integer
Unsigned
1
R/W
Integer
Unsigned
1
R/W
Integer
ModBUS Register Information
Description
Sets the controller phase
(0 = Low; 1 = High)
Sets the controller deadband
Sets the overfeed timer value (mins)
Sets the on delay time (sec)
Sets the off delay time (sec)
Resets the overfeed timer
Sets the event setpoint
Sets the event phase (0 = Low; 1 = High)
Sets the event deadband
Sets the max on time (mins)
Sets the min on time (mins)
Sets the max off time (mins)
Sets the min off time (mins)
Sets which Sensor outputs are affected
during timer on time (0 = None;
2 = Selected Sensor; 13 = All Sensors)
Selects which Sensor outputs are being
held/transferred during the timers on time
(this is used when Hold type is set for
single Sensor)
Selects hold outputs vs. set transfer value
during timers on time
Sets the timer on duration time (sec)
Sets the period between timer on events
(mins)
Sets the time the affected Sensor outputs
are held/transferred after the timer turns
off (sec)
Sets the status level which will trigger the
relay
Selects data source for this relay
(0 = None; 1 = Real Time Clock;
2 = Sensor; 4 = Calculation)
Selects Sensor source when Source
= Sensor (0 = Sensor1; 1 = Sensor2)
Selects measurement on the Sensor
(0 = Meas1 .. 3 = Meas4)
63