Wiring the Wallbox Power Module with DALI Control Unit:
IEC PELV/NECR Class 2 Wiring Details (HomeWorksR QS only)
The WPM can be configured for wired/QS
link (HomeWorksR QS only) or wireless/
RF link (RadioRAR 2 and HomeWorksR
QS) communication. The following
diagram illustrates wiring the device to
a QS link. HomeWorks
R
QS supports
selection of wired or RF communications.
A Wallbox Power Module main unit that
communicates back to a HomeWorks
QS processor through the RF link should
not have any QS wired link connections.
In RadioRA
R
2 only RF communication is
available
WARNING! Shock hazard. May
result in serious injury or death.
Always turn off circuit breaker or
remove main fuse from power line
before doing any work.
Step 1: Strip 25 mm of insulation from
the IEC PELV/NECR Class 2 cable.
Step 2: Strip 7 mm of insulation from
each wire in the cable.
Step 3: Connect the wires to the QS Link
terminal block, making sure no bare wire
is exposed after making the connections.
The recommended installation torque is
0.4 N•m for QS Link connections.
®
R
IEC PELV / NECR Class 2 control
wiring: 0.75 mm
HomeWorksR QS Link 610 m
maximum total wire length
per run
DO NOT CONNECT PIN 2
Data link: twisted, shielded pair
0.34 mm
To additional QS devices
Note: The QS Link IEC PELV/NECR
Class 2 cable and terminal block should
be separated from the line voltage/mains
cables by at least 6 mm.
D1 D1 D2 D2
2
2
to 0.75 mm
2
Pin 2 does not get connected to the
WPM – it does not require link power
Note: The QS Link IEC PELV/NECR
Class 2 cable and terminal block should be
separated from the DALI Link wires.
Wallbox Power Module Installation and Operation Guide 5