Lutron DALI LOR-WPM-6D Guía De Instalación Y Funcionamiento página 4

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 13
Wiring the Wallbox Power Module with DALI Control Unit:
DALI-Compliant Bus Wiring Details
• DALI terminal block is double insulated
from QS and mains voltage terminals.
• DALI bus wiring may be run in the same
conduit as mains wiring.
• Lutron recommends using two different
colors for D1 and D2 (DALI bus) wires.
This will prevent wiring mistakes in
junction boxes where several different
DALI bus wires combine. Use the
following instructions for wiring the DALI
bus.
• Each DALI bus link can have only 1
Wallbox Power Module (WPM) with DALI
control unit connected to it. No additional
DALI supplies can be on the link.
• Up to 64 DALI devices can be connected
to the DALI bus.
• No other devices may be connected to
the DALI link.
WARNING! Shock hazard.
May result in serious injury or
death. Do not wire live. Always
turn off circuit breaker or remove
main fuse from power line before
wiring and servicing the Wallbox
Power Module.
®
Step 1: Use the wire size chart at right to
determine which wire size to use based
on the length of the DALI bus.
Step 2: Wire the DALI bus from terminal
D1 and terminal D2 to all DALI devices.
Step 3: Turn on circuit breaker to
energize.
DALI Bus
18 V-
250 mA
Wiring Size and Bus Length
DALI bus wires D1 and D2 are not
polarity sensitive. DALI bus length is
limited by the wire gauge used for D1 and
D2 as follows:
Wire Gauge
1.5 mm
0.75 mm
0.50 mm
Note: Some DALI devices (ballasts,
drivers, and interfaces) accept
connections to daylight sensors
and occupancy sensors. For
instructions on installing and
operating these devices, refer to
their individual instruction sheets.
Wallbox Power Module Installation and Operation Guide 4
Maximum DALI
Bus Length
300 m
2
150 m
2
100 m
2
Tabla de contenido