The following table indicates the function of each pin of the 10-pin terminal:
The following table identifies the function of each relay on the card:
3 109 69 Dry contact card
1
Bypass
2
Mains absent (Normally Open)
3
Mains present (Normally Closed)
4
Inverter ON
5
Battery low
6
Battery fail
7
Generic Alarm
8
COMMON
9
Input Signal remote UPS shutdown (+)
10
Input Signal remote UPS shutdown (-)
Relay
Description
K1
Bypass
K2
Mains absent
K3
Inverter ON
K4
Battery low
K5
Battery fail
K6
Generic alarm
Status
depends on JP1
Normally Closed
(pin 3 - mains present)
Normally Open
(pin 2 - mains absent)
depends on JP2
depends on JP3
depends on JP4
depends on JP5
13