MR TAPCON 230 expert Manual Del Usuario página 16

Regulador de tensión
Ocultar thumbs Ver también para TAPCON 230 expert:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Attribute
Attribute
Name
Type
HiCtlV
MV
LoCtlV
MV
HiDmdA
MV
Status Information
Auto
SPS
HiTapPos
INS
LoTapPos
INS
Ajustes
BndCtr
ASG
BndWid
ASG
CtlDlTmms
ING
LDCR
ASG
LDCX
ASG
BlkLV
ASG
BlkRV
ASG
RnbkRV
ASG
LimLodA
ASG
LDC
SPG
TmDlChr
SPG
LDCZ
ASG
VRedVal
ASG
16
TAPCON® 230 expert
ATCC class (ATCC1)
Explanation
Highest Control Voltage
Lowest Control Voltage
High current demand (Load Cur-
rent Demand)
Automatic/Manual operation
High tap position
Low tap position
Actual band center voltage (FPF
presumed)
Can't be set.
Only available if transformer pri-
mary voltage is set.
Band width voltage (as voltage or
percent of nominal voltage, FPF
presumed)
Control intentional time delay (FPF
presumed)
Line drop voltage due to line resis-
tance component
Line drop voltage due to line reac-
tance component
Control voltage below which auto
Lower commands blocked
Control voltage above which auto
Raise commands blocked
Runback Raise Voltage
Limit Load Current (LTC Block
Load Current)
Line Drop Compensation is R&X
or Z model
Time delay linear or inverse cha-
racteristic
Line drop voltage due to line total
impedance
Reduction of band centre (percent)
when voltage step 1 is active
2664024/01 ES
4 Puntos de entrada de datos
Extra
used
T
Attribute
N
N
N
N
N
N
N
Y
N
N
N
N
N
Y
N
Y
N
Y
N
Y
N
Y
N
Y
N
N
N
N
N
Y
N
Y
N
Y
N
Y
N
N
© Maschinenfabrik Reinhausen 2012
M/O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O

Hide quick links: