Toshiba MMY-MAP0804HT5P Manual De Instalación página 12

Ocultar thumbs Ver también para MMY-MAP0804HT5P:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Pipe
Type
D
a r
w
o -
diameter
Cut the L-shaped pipe at the horizontal straight
section, then braze the supplied attachment
pipe, and the socket and pipe procured locally.
MAP140
Liquid
Ø28.6
MAP160
pipe
Attachment pipe
Balance
pipe
Extruding margin of copper pipe with flare machining: B (Unit: mm)
Copper pipe outer
When using R410A
dia.
tool
9.5
12.7
0 to 0.5
15.9
Extruding margin of copper pipe with flare tools: A (Unit: mm)
+0
Copper pipe outer dia.
A
-0.4
9
5 .
1
3
2 .
1
2
7 .
1
6
6 .
1
5
9 .
1
9
7 .
* When using the conventional flare tool, to connect R410A pipes with flaring, make a margin approx. 0.5mm
longer than that of an R22 pipe so that the flare size matches the one specified. It is convenient to use a copper
pipe gauge for size adjustment of the extruding margin.
CAUTION
Wrap the ball valve in a wet cloth to keep it cool and prevent the heat from the
torch from damaging it when connecting the pipe to the ball valve on the gas line.
21-EN
1114208701-1 EN PT ES.indb 11
1114208701-1 EN PT ES.indb 11
u
f t
r o
w
a
d r
D
a r
w
o -
t u
d
o
w
n
w
a
d r
Cut the L-shape pipe at the vertical straight
section, then braze the supplied attachment
pipe, and the socket and pipe procured locally.
Gas
pipe
Liquid
Gas pipe
Gas pipe
pipe
Attachment
Balance
pipe
pipe
Socket
Socket
Pipe
Pipe
Section
to be cut
When using
conventional tool
1.0 to 1.5
A
– 11 –
Coupling size of brazed pipe
Connected section
External size
K
Gas
pipe
Section
to be cut
External size
Standard outer dia.
of connected
copper pipe
6.35
6.35 (±0.03)
9.52
9.52 (±0.03)
12.70
12.70 (±0.03)
15.88
15.88 (±0.03)
19.05
19.05 (±0.03)
22.22
22.22 (±0.03)
28.58
28.58 (±0.04)
34.92
34.90 (±0.04)
38.10
38.10 (±0.05)
41.28
41.28 (±0.05)
Selection of pipe size
Capacity code of indoor and outdoor units
Selection of pipe material
For the indoor unit, the capacity code is decided at each capacity rank. (Table 1)
The capacity codes of the outdoor units are decided at each capacity rank. The maximum number of connectable
indoor units and the total value of capacity codes of the indoor units are also decided. (Table 2)
NOTE
Cloth
Compared with the capacity code of the outdoor unit, the total value of capacity codes of the connectable indoor units differs
based on the height difference between the indoor units.
Torch
When the height difference between the indoor units is 15m or less: Up to 135% of the capacity code (Equivalent
to HP) of the outdoor unit (Equivalent to HP) of the outdoor unit
When the height difference between the indoor units is over 15m: Up to 105% of the capacity code
Internal size
G
Connected section
Internal size
Min. depth of
Standard outer dia.
insertion
Oval value
(Allowable difference)
C
F
K
G
6.45 (
+0.04
)
7
6
0.06 or less
-0.02
+0.04
9.62 (
)
8
7
0.08 or less
-0.02
12.81 (
+0.04
)
9
8
0.10 or less
-0.02
+0.04
16.00 (
)
9
8
0.13 or less
-0.02
19.19 (
+0.03
)
11
10
0.15 or less
-0.03
+0.03
22.36 (
)
11
10
0.16 or less
-0.03
28.75 (
+0.06
)
13
12
0.20 or less
-0.02
+0.04
35.11 (
)
14
13
0.25 or less
-0.04
38.31 (
+0.08
)
15
14
0.27 or less
-0.02
+0.08
41.50 (
)
15
14
0.28 or less
-0.02
(Unit: mm)
Min. thickness
of coupling
0.50
0.60
0.70
0.80
0.80
0.82
1.00
1.20
1.26
1.35
22-EN
02/27/14 1:39 PM
02/27/14 1:39 PM