Daikin UATYQ250MCY1 Manual De Instalación página 26

Ocultar thumbs Ver también para UATYQ250MCY1:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 173
The diagram below shows the position for terminal blocks in the controller main board which are used for
thermostat control and BMS system. Beside that, the output pins for auxilliary electrical heater are shown as well.
Thermostat Control (TB_THM-l)
Connect to
third party
controller
BMS System (TB_BMS-l)
Connect to
BMS
System
(iv) Auxilliary Electrical Heater Output (HTR1 and HTR2)
ü
There are two output pins (HTR1 and HTR2) on controller main board, which are used to energize the heater
contactor. The contactor must be selected accordingly to avoid any safety issue(s).
ü
The heater shall be installed in accordance with local and national legislation. It must comply with EN60335-2-40.
ü
Thermal fuse(s) shall be installed on the heater to eliminate any danger or damage on the heater/unit. This is
especially critical when there is any malfunction happen to controller main board or blower.
ü
The heater shall be in a safe location, whereby no risk of damage could be happen on the unit.
ü
Use non-fl ammable duct for the unit that is installed with heater
ü
Use diff erent power supply for electrical heater and install a circuit breaker for each of the heater.
ü
Maximum temperature in the unit must not exceed 60°C. Temperature measurement shall be taken during the
installation or commisioning in order to ensure the temperature not exceed this value.
ü
Select the proper safety device or thermal protector accordingly.
ü
The heater shall never be installed inside the unit. The recommended location for the heater is inside the supply
duct, whereby the distance of the heater is suffi cient to ensure the temperature inside the unit does not exceed
60°C.
(v) Economizer control
ü
Ensure the economizer kit has been incorporated with rooftop unit before activate the economizer function in
the controller main board. Else, error will occur.
ü
To activate economizer function, set Dip Switch Setting: SW4 - ON (default is OFF) in the controller main board
and panel parameter G6 to '1' (default is '0').
G6 = Economizer control
0 = disable
1 = enable.
ü
In economizer controller board, there are 4 dip switches and 3 shunt jumpers which provide fl exible selection
based on diff erent requirements:
– Dip Switch 1: Minimum fresh air opening setting in heating mode, where by the selection of diff erent pins will
– Dip Switch 2: Minimum fresh air opening setting in cooling mode, where by the selection of diff erent pins will
– Dip Switch 3: CO
– Dip Switch 4: Type of operation, which include the following selection:-
24
give diff erent opening setting. SW1: 5%, SW2: 10%, SW3: 15%, SW4: 20%, SW5: 25%, SW6/7/8:
no function, Default: 0% (no selection, all OFF).
give diff erent opening setting. SW1: 0%, SW2: 5%, SW3: 15%, SW4: 20%, SW5: 25%, SW6/7/8:
no function, Default: 10% (no selection, all OFF).
PPM level threshold value selection, where by the selection of diff erent pins will give
2
diff erent value setting. SW1: 25%, SW2: 50%, SW3: 75%, SW4: 100%, Default: 0% (no selection,
all OFF).
SW1: OFF = Diff erential temperature operation (default), ON = No function at this moment.
SW2: OFF = Economizer mode (default), ON = Fresh air mode.
SW3: OFF = Overcooled protection is activated (default), ON = Overcooled protection is not
activated.
Dry Contact Outputs (TB_BMS-O)
Defrost
Alarm
Output
Output
signal
output
(AL)
1 (O1)
2 (O2)
(DFRT)
Controller Main Board
Heater Output (HTR1 and HTR2)
Connect to
Connect to
heater
heater
contactor
contactor
ON
OFF
1
2
3
4
5
6
7
8

Hide quick links:

Capítulos

Tabla de contenido
loading

Este manual también es adecuado para:

Uatyq350mcy1Uatyq450mcy1Uatyq550mcy1Uatyq600mcy1Uatyq700mcy1

Tabla de contenido