HAzARD
EXPLOSION
STATIC ELECTRICITY
Use of this equipment in
a potentially explosive
atmosphere.
Vapors from flammable
liquids can catch fire
or explode from static
electricity discharges.
SPECIAL
Over pressurization of
CONDITIONS
equipment can cause
FOR SAFE USE
equipment failure or injury.
REQUIRED
Use lubricating medium
BY ATEX
resistant to carburisation.
CERTIFICATION
Improper operation or
maintenance may create a
hazard.
EC Declaration of Conformity
We: Finishing Brands, Ringwood Rd., Bournemouth, Dorset, BH11 9LH, UK
As the manufacturer of the items listed below:
Declare, under our sole responsibility, that, the equipment to which this document relates is in conformity with the fol-
lowing standards or other normative documents:
EN 13463-1:2009, EN 13463-5:2005, EN 982:1996 + A1:2008, EN 983:1996 + A1:2008 and EN 12621:2006
And thereby conform to the protection requirements of Council Directive 98/37/EC relating to Machinery Safety Directive and
council Directive 94/9/EC relating to Equipment and Protective Systems intended for use in Potentially Explosive
Atmospheres;
Issued on: 1st July 2009
Authorized by:
General Manager
Technical file lodged with;
TRL Compliance Ltd (Notified Body 0891)
Moss View
Nipe Lane
Up Holland
WN8 9PY, UK
4
CAUSE
1. If installing this equipment in a potentially explosive
2. Check electrical continuity of the air supply to earth —
3. Electrically bond all metallic equipment to earth.
1. Do not exceed the stated maximum working pressures
2. Only a suitably approved static dissipating or
3. Air supplies (compressors, etc.) shall be sited in a non-
4. Use lubricating medium resistant to carburisation and
5. User shall ensure all metallic parts of the equipment
Piston Pumps
MX412
CE Ex 2 II Gc T4
SAFEGUARDS
atmosphere, check the ATEX equipment category and
temperature ratings meet the requirements for the
zoned area.
should be no greater than 10
Should be no greater than 1 .
and motor speed as specified in this manual.
conductive air supply hoses shall be attached to the
equipment and terminated to the air supply.
hazardous area with a filter on the air intake system to
prevent the ingress of dust or similar foreign material
into the parts where compression takes place.
has an auto ignition temperature of more than 185ºC
for T4 equipment.
are suitably bonded to earth. Should be no greater
than 1 .
MX432