Function
55
Last trip
56
55
Trip before Pr
57
56
Trip before Pr
58
57
Trip before Pr
Indicates the last 4 trips of the drive.
No
Function
59
PLC ladder program enable
The PLC ladder program enable is used to start and stop the PLC ladder program.
0: Stop the PLC ladder program
1: Run the PLC ladder program (trip drive if LogicStick is not fitted). Any out-of-range
parameter writes attempted will be limited to the maximum/minimum values valid for
that parameter before being written to.
2: Run the PLC ladder program (trip drive if LogicStick is not fitted). Any out-of-range
parameter writes attempted will cause the drive to trip.
See the Digidrive SK Advanced User Guide for details on PLC ladder programming.
No
Function
60
PLC ladder program status
The PLC ladder program status parameter indicates the actual state of the PLC ladder
program.
-n: PLC ladder program caused a drive trip due to an error condition while running rung
n. Note that the rung number is shown on the display as a negative number.
0: LogicStick is fitted with no PLC ladder program
1: LogicStick is fitted, PLC ladder program is installed but stopped
2: LogicStick is fitted, PLC ladder program is installed and running
3: LogicStick is not fitted
No
Function
61
Configurable parameter 1 to
to
configurable parameter 10
70
Pr 61 to Pr 70 and Pr 71 to Pr 80 can be used to access and adjust advanced
parameters.
Example: It is desired that Pr 1.29 (Skip frequency 1) is to be adjusted. Set one of the
parameters Pr 71 to Pr 80 to 1.29, the value of Pr 1.29 will appear in the corresponding
parameter from Pr 61 to Pr 70. I.e. if Pr 71 is set to 1.29, Pr 61 will contain the value of
Pr 1.29 where it can be adjusted.
Some parameters are only implemented if the drive is disabled, stopped or tripped and
NOTE
the
STOP/RESET key is pressed for 1s.
See Digidrive SK Advanced User Guide for advanced parameter details.
Digidrive SK Getting Started Guide
Issue Number: a
English
Deutsch
Italiano
Range
Range
0 to 2
Range
-128 to +127
Range
As source
Español
Defaults
Type
0
RO
Defaults
Type
0
RW
Defaults
Type
RO
Defaults
Type
79