Troubleshooting
(For further information, visit the www.powerquality.eaton.com site or contact after-sales
support.)
Problem
1
The battery backup outlets 9 are
l
not supplied with power.
2
The connected devices are not
l
supplied when AC power fails.
3
AC power is available, but the
l
UPS operates on battery power.
4
The filtered outlets 8 are not
l
supplied.
5
Green button 12 flashes
l
frequently and audio alarm beeps.
6
12
Green button
flashes and audio
l
alarm beeps continuously.
7
Red LED 11 is on and the audio
l
alarm beeps every 30 seconds.
8
Green LED 10 is off and the
l
filtered outlets 8 are supplied.
9
The telephone line is disturbed or
l
modem access is not possible.
10
Red LED 11 flashes.
l
11
EcoControl outlets keep powered
l
when main application (Master
outlet) is stopped.
Advanced customizing of your UPS
Sensitivity to variations of the AC power supply
Only to be used if frequent switching to the UPS
l
battery due to large variations in the AC supply
voltage.
Accessing the programming mode: with the device
l
switched off, press button 12 for 6 s and release it
once LEDs 10 11 have come on.
Display of the 3 possible voltage ranges according to
l
the status of LEDs 10 and 11 :
Normal mode
Low range
(factory
mode:
configuration):
AC supply
AC supply
between 161V
between 184V
and 264V
and 264V
11
12
11
11 10
12
11 10
Change from one mode to another by successively
pressing button 12 .
Memorizing the mode: 10 s after the last press of the
l
button.
614-06803-00
Diagnostic
Button 12 is not lighted on.
l
The devices are not connected to
l
the battery backup outlets 9 .
Circuit breaker 13 , located under
l
the UPS, has been tripped by an
overload on the UPS output.
The wall outlet is not supplied.
l
Circuit breaker 13 , located under
l
the UPS, has been tripped by an
overload on the UPS output.
The UPS frequently operates
l
on battery power because the AC
power source is of poor quality.
The UPS battery backup outlets
l
9 are overloaded.
A fault has occurred on the UPS.
l
The battery backup outlets 9 are
no longer supplied.
Surge protection is no longer
l
provided.
Surge protection on the telephone
l
line is no longer provided.
The battery has reached the end
l
of its service life.
EcoControl function is not
l
activated or not properly set.
Low and high
range mode:
AC supply
between 161V
and 284V
12
11
12
12
11 10
12
Solution
Press button 12 and check that it
l
turns green.
Connect the devices to the battery
l
backup outlets 9 .
Disconnect excess equipment
l
and reset the circuit breaker 13 by
pressing the corresponding button.
Supply power to the wall outlet.
l
Disconnect excess equipment
l
and reset the circuit breaker 13 by
pressing the corresponding button.
Have the electrical installation
l
checked by a professional or use
another wall outlet.
Disconnect excess equipment
l
connected to the battery backup
outlets 9 .
Call after-sales support.
l
Call after-sales support.
l
Disconnect the telephone line
l
from the wall outlet.
Call after-sales support.
l
Have the battery replaced.
l
Activate or set properly
l
EcoControl function using the
software provided with the product.
Audio alarm
Possibility of deactivating the audio alarm when the
l
UPS is operating on the battery.
Accessing the programming mode: with the device
l
switched off, press button 12 for 11 s and release it
when the audio alarm sounds.
Display of the 2 possible audio alarm modes:
l
Normal mode (factory
configuration):
the UPS emits a beep
every 10 s when operating
on its battery.
Normal mode
activated:
programming by
continuous beep.
Change from one mode to another by successively
pressing button 12 .
Memorizing the mode: 5 s after the last press of the
l
button.
Silent mode:
the UPS emits a single
beep when switching to
battery operation and
then remains silent.
Silent mode
activated:
programming by a
beep every second.
7