6.2 TECHNICAL DATA - STANDARD VERSION (H) 3N 400V ~ 50Hz
FLOOR SYSTEM HEATING MODE (1)
Heating capacity
Total input power
COP
Water flow rate
Pressure drop
Input current
FAN COIL OPERATION (2)
Heating capacity
Total input power
COP
Water flow rate
Pressure drop
Total input power
RADIATOR OPERATION AT LOW TEMPERATURES (3)
Heating capacity
Total input power
COP
Water flow rate
Pressure drop
Total input power
COOLING MODE (3)
Cooling capacity:
Total input power
EER
Water flow rate
Pressure drop
Total input power
ELECTRICAL DATA
Total starting current
Compressor starting current
1
2
Compressor starting current
Compressor maximum input power 1
Compressor maximum input power 2
Maximum total input power
COMPRESSORS
Types
Circuit compressors
Capacity step control
FANS
Types
Quantity
Air flow rate
CONDENSER
Types
Quantity
HYDRAULIC CONNECTIONS
IN/OUT connections
SOUND DATA
Sound pressure in heat mode
Sound power in heat mode
Sound pressure in cooling mode
Sound power in cooling mode
DIMENSIONS
Height
Width
Depth
H weight
Heating (1)
FLOOR SYSTEM
processed water temperature
35°C;
external air temperature
7°C D.B./6°C W.B.;
Dt =
5°C.
Heating (2)
FAN COILS
processed water temperature
45°C;
external air temperature
7°C D.B./6°C W.B.;
Dt =
5°C.
U.M.
kW
kW
kW/kW
l/h
kPa
A
kW
kW
kW/kW
l/h
kPa
A
kW
kW
kW/kW
l/h
kPa
A
kW
kW
kW/kW
l/h
kPa
A
A
A
A
A
A
A
-----
no.
%
-----
no.
m3/h
-----
no.
Ø F
dB(A)
dB(A)
dB(A)
dB(A)
mm
mm
mm
kg
Heating (3)
RADIATORS AT LOW TEMPERATURES
processed water temperature
55°C;
external air temperature
7°C D.B./6°C W.B.;
Dt =
5°C.
Cooling (4)
outlet water temperature
7°C;
external air temperature
35°C
Dt =
5°C.
0502
0802
13.77
17.22
3.72
4.55
3.70
3.78
2360
2960
20
30
8. 1
10.0
13.05
16.41
4.33
5.28
3.01
3. 1 0
2240
2820
18
28
8.8
10.8
12,36
15.42
5.06
6.28
2.44
2.46
2360
2960
20
30
10.30
12.95
11.90
14.40
4.40
5.30
2.70
2.72
2050
2480
15
22
9.4
11.5
37
52
26
32
32
46
5
6
7
9
13.7
16.7
scroll
scroll
2 / 1
2 / 1
40-60-100
40-60-100
axial
axial
2
2
6550
6450
plates
plates
1
1
1" 1/4
1" 1/4
39.5
40.0
71.5
72.0
41.0
39.0
73.0
71.0
1580
1580
1277
1277
555
555
223
232
Sound power:
Aermec determines the value of the sound
power on the basis of measurements taken
in accordance with the ISO/DS 9614-2
standard in compliance with what is requi-
red by the Eurovent certification.
Sound pressure:
Sound pressure in unrestricted range on
reflecting plane (directionality fact. Q=2), at
10 m distance from the outer surface of the
unit. Complying with the standard ISO3744.
N.B.
Data stated according to: EN 14511:2004
0902
20.96
5.48
3.82
3610
36
11.7
20.0
6.48
3.09
3440
33
12.9
18.85
7.57
2.49
3610
36
15.06
17.80
6.60
2.70
3060
26
14.0
58
46
51
9
11
21.7
scroll
2 / 1
50-100
axial
2
6450
plates
1
1" 1/4
40.0
72.0
35.5
67.5
1580
1277
555
247