Display Turned "Off; Relay Latching - Macurco CD-6B Instrucciones Del Usuario

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Macurco CD-6B Manual (Rev-1.0) Eng
Clean Air – and in clean air, the display will show the current concentration of CO
Note: CO
in "clean air" will not show 0 as normal atmospheric CO
2
Awareness Alarm - and the CO
will sound (beep every 60 seconds) if "bUZ" is turned "On".
Alarm 1 level – and the CO
"ALr1" and "current gas reading". The buzzer will sound (beep every second) if "bUZ" is turned "On".
Alarm 2 level – and the CO
"ALr2" and "current gas reading". The buzzer will sound (beep every second) if "bUZ" is turned "On".
Alarm 3 level – and the CO
"ALr3" and "current gas reading". The buzzer will sound (beep every second) if "bUZ" is turned "On".
Trouble –and the device in a trouble state, the display will show the "t" Error code (t01 for example). If the
Trouble Fan Setting "tFS" is enabled, the Alarm 1 Relay will activate. See section
section
4.5.11 Trouble Fan Setting –
Calibration Due – With Calibration Period functionality enabled, if a detector is within 1 month of calibration
period, the display will flash between "dUE" and current gas reading. Calibration Due is resolved only with a
successful field calibration.

4.6.3 Display turned "Off"

With the display function turned off,
Clean Air – and in clean air, the display does not show the CO
on will be on.
Awareness Alarm - and the CO
sound (beep every 60 seconds) if "bUZ" is turned "On".
Alarm 1 Level – and the CO
The buzzer will sound (beep every second) if "bUZ" is turned "On".
Alarm 2 Level – and the CO
The buzzer will sound (beep every second) if "bUZ" is turned "On".
Alarm 3 Level – and the CO
The buzzer will sound (beep every second) if "bUZ" is turned "On".
Trouble – and the device in a trouble state, the display will display the "t" Error code (t01 for example). If
the Trouble Fan Setting "tFS" is enabled, the Alarm 1 Relay will activate. See section
and section
4 .5.11 Trouble Fan Setting – "tFS".
3 1 T
Calibration Due – With Calibration Period functionality enabled, if a detector is within 1 month of calibration
period, the display will show "dUE" continuously. Calibration Due is resolved only with a successful field
calibration.

4.7 Relay Latching

Each alarm relay has the relay latching option. This controls the alarm behavior after an alarm has been activated
and the gas concentration returns below the alarm level.
Latching On – When the relay latching option is set to "On" and the gas concentration triggers the alarm, the relay
will not deactivate when the gas concentration drops below the alarm level. The power will need to be interrupted
or the "ENTER/TEST" button pressed to un-latch (turn off) the relay condition.
REV – 1.0
percentage reaching 0.50%, the display will flash "gas reading". The buzzer
2
percentage reaching the Alarm 1 Relay setting, the display will flash between
2
percentage reaching the Alarm 2 Relay setting, the display will flash between
2
percentage reaching the Alarm 3 Relay setting, the display will flash between
2
"tFS".
percentage reaching 0.50%, the display will show nothing. The buzzer will
2
percentage reaching the Alarm 1 Relay setting, the display will show "ALr1".
2
percentage reaching the Alarm 2 Relay setting, the display will show "ALr2".
2
percentage reaching the Alarm 3 Relay setting, the display will show "ALr3".
2
[34-2900-0510-2 ]
in the air.
2
levels are between 0.03% and 0.05%.
2
5.1.2 "t" Error Codes
concentration. Only the Power indicator light
2
5 .1.2 "t" Error Codes
3 1 T
and
3 1 T
3 1 T
14 |