Macurco CD-6B Manual (Rev-1.0) Eng
NOTE: The Awareness Alarm has the lowest alarm priority.
4.3 Alarm 1 Relay
To set the Alarm 1 Relay set point, use the "A1S" setting in the Configuration menu. The selectable values
•
are "diS", 0.25, 0.50 (default), 1.00, 1.50, 2.00, 2.50, 3.00, 3.50, 4.00, 4.50, 5.00.
The Alarm 1 Relay can be triggered by an instantaneous reading or a time weighted average. This can be
•
selected via the "A1t" setting in the Configuration menu. The time weighted average uses readings over the
previous 8-hour period to calculate the average. The default setting is "On".
•
The Alarm 1 Relay can be configured to nO or nC. Default is nO. This can be changed via the "A1c" setting in
the Configuration menu.
To set the Alarm 1 latching behavior, use the "A1L" setting in the Configuration menu. Default is non-
•
latching "OFF".
If the "tFS" setting is "On" the Alarm 1 Relay will engage during a trouble condition. The default setting is
•
"OFF". The "tFS" setting can be changed in the Configuration menu.
Electrical Ratings: SPST to switch 2 A load, up to 240 VAC or 30 VDC
•
4.4 Alarm 2 Relay
•
To set the Alarm 2 Relay set point, use the "A2S" setting in the Configuration menu. The selectable values
are "diS", 0.25, 0.50, 1.00, 1.50 (default), 2.00, 2.50, 3.00, 3.50, 4.00, 4.50, 5.00.
•
The Alarm 2 Relay can be configured to nO or nC. Default is nO. This can be changed via the "A2c" setting in
the Configuration menu.
•
To set the Alarm 2 latching behavior, use the "A2L" setting in the Configuration menu. Default is non-
latching "OFF".
The Alarm 2 relay responds to instantaneous gas reading only (no time weighted average option).
•
•
Electrical Ratings: SPST to switch 2 A load, up to 240 VAC or 30 VDC
4.5 Alarm 3 Relay
To set the Alarm 3 Relay set point, use the "A3S" setting in the Configuration menu. The selectable values
•
are "diS", 0.25, 0.50, 1.00, 1.50, 2.00, 2.50, 3.00 (default), 3.50, 4.00, 4.50, 5.00.
•
To set the Alarm 3 latching behavior, use the "A3L" setting in the Configuration menu. Default is latching
"ON".
•
The Alarm 3 Relay can be wired to nO or nC. This can only be changed by wiring.
The Alarm 3 Relay responds to instantaneous gas reading only (no time weighted average option).
•
•
Electrical Ratings: SPDT to switch 2 A load, up to 240 VAC or 30 VDC
4.6 Alarm Behavior
4.6.1 Alarm Priority
From lowest to highest, the alarm priority is as follows: Awareness Alarm, Alarm 1, Alarm 2, Alarm 3, Trouble Fault.
For example, the trouble condition has the highest priority. Therefore, when there is an occurrence of an alarm and
a trouble condition at the same time, the unit behavior (buzzer, display and power LED) will follow the trouble
condition.
4.6.2 Display turned "On"
With the display function turned "On",
REV – 1.0
[34-2900-0510-2 ]
13 |
P a g e