Installation
PARAMETER
FEATURE
NUMBER
ECO HEAT
114
TEMPERATURE
REDUCTION
COOL WATER
115
SET-POINT
ECO COOL
116
TEMPERATURE
REDUCTION
COOL CLIMATIC
117
NUMBER
MIN OUTDOOR
118
AIR TEMPERATURE
HEATING
MAX OUTDOOR
119
AIR TEMPERATURE
HEATING
MIN WATER
120
TEMPERATURE
HEATING
MAX WATER
121
TEMPERATURE
HEATING
MAX OUTDOOR
122
AIR TEMPERATURE
COOLING
MIN OUTDOOR
123
AIR TEMPERATURE
COOLING
MIN WATER
124
TEMPERATURE
COOLING
MAX WATER
125
TEMPERATURE
COOLING
OAT
126
THERMISTOR
TO SENSOR VALUE
( )
127
TE SENSOR VALUE
( )
128
TS SENSOR VALUE
( )
129
TD SENSOR VALUE
( )
130
CDU MODE
( )
131
MAX COMPRESSOR
( )
132
FREQUENCY
REQUESTED
( )
133
FREQUENCY
REAL FREQUENCY
( )
134
COMPRESSOR
( )
135
RUNTIME
DESCRIPTION
This code is use to set the temperature reduction value
for fixed heating water set-point when the unit is in
ECO mode.
This code is use to set the fixed cooling water set-point.
This code is use to set the temperature reduction value
for fixed cooling water set-point when the unit is in ECO
mode.
This code is use to select the cool climatic curve
number:
0. No predefined climatic curve (Installer has to draw CC)
1 - 2. Refers to UI manuals for climatic curve details
This code is use to select the minimum outdoor
temperature of the heating climatic curve, depending
on the country where the system is installed.
This code is use to select the maximum outdoor
temperature of the heating climatic curve.
This code is use to select the minimum water
temperature of the heating climatic curve.
This code is use to select the maximum water
temperature of the heating climatic curve.
This code is use to select the maximum outdoor
temperature of the cooling climatic curve, depending
on the country where the system is installed.
This code is use to select the minimum outdoor
temperature of the cooling climatic curve.
This code is use to select the minimum water
temperature of the cooling climatic curve.
This code is use to select the maximum water
temperature of the cooling climatic curve.
This code is use to define if
thermistor is installed or not
1.
thermistor installed
thermistor not installed
2.
This code displays the outdoor air temperature value
read by the TO sensor.
This code displays the refrigerant temperature value
read by the TE sensor.
This code displays the suction temperature value read
by the TS sensor.
This code displays the discharge temperature value read
by the TD sensor.
This code displays the actual Heat Pump operating
mode:
0. Off
2. Cool
3 Heat
4. Fail
5. Defrost
This code displays the maximum compressor
frequency calculated by
This code displays the requested frequency by the
system control.
This code displays the real compressor frequency
This code displays the working on hours (x10) of the
compressor.
VALUE
RANGE
Min
1°C
4°C
1°C
0
-20°C +10°C
10°C
20°C
20°C
24°C
0°C
4°C
4°C
OAT
1
-
-
-
-
-
-
control board.
-
-
-
STANDARD
Max
20°C
5°C
25°C
7°C
10°C
5°C
2
0
-7°C
30°C
20°C
60°C
40°C
60°C
55°C
46°c
40°C
30°C
22°C
20°C
4°C
20°C
12°C
2
2
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
7