WITCHING ON FROM THE MAINS
 Close the SWIN and SWBYP input switches (if present) and leave the SWMB manual bypass switch open.
After a few seconds, the UPS will switch on and the "Stand-by / alarm" LED will flash: the UPS is now in stand-by status.
8
 Press
to access the start menu. When asked to confirm, select "YES" and press
around the display will light up for about 1 sec. and a beep will be emitted. The start sequence is completed when the UPS is
set to status with the inverter-powered load.
S
WITCHING ON FROM THE BATTERY
 Ensure that the external UPS battery line switch/fuses are closed
 Keep the "Cold Start" (located behind the door) key pressed for about 5 sec. The UPS will switch on and the display will turn
on.
8
 Press
to access the start menu. When asked to confirm, select "YES" and press
around the display will light up for about 1 sec. and the buzzer will begin to emit a beep every 7 sec. The start sequence is
completed when the UPS is set to battery operation status.
Note: if the sequence described above is not performed within 1 min., the UPS will shut itself off to avoid unnecessary running
down the battery
S
HUTDOWN
From the main menu, select the item "SHUTDOWN" and press
8
option and press
the UPS, open the SWIN and SWBYP input switches (if present), wait a few seconds while the display turns off and, finally,
open the external UPS battery line switch/fuses.
88
. The UPS will be set to stand-by status and the load will no longer be powered. To completely switch off
8
to access the sub-menu. Then select the "YES - CONFIRM"
8
again to confirm. All the LEDs
8
again to confirm. All the LEDs