UPS Models
INPUT STAGE
Nominal Voltage
Nominal Frequency
Maximum input current
Maximum battery current
Input voltage tolerance accepted for no
battery intervention (referred to 400V AC)
Input frequency tolerance accepted for no
battery intervention (referred to 50/60Hz)
Input current Harmonic Distortion
Input power factor
Power Walk In mode
OUTPUT STAGE
(3)
Nominal Voltage
(4)
Nominal Frequency
Output nominal current
Nominal apparent power in output
Nominal active power in output
Output power factor
Short-circuit current
Output voltage precision (referred to output
voltage 400V AC)
(5)
Static stability
Dynamic stability
Output voltage harmonic distortion with linear
load and normalized distortion
Crest factor accepted at nominal load
Frequency accuracy in free running mode
Inverter overload (Vin>345V AC )
Bypass Overload
BATTERY CHARGE STAGE
Nominal voltage
Maximum recharging current
108
TECHNICAL DATA
(1)
≤ 1% with linear load
≤ 3% with distorted load
(7)
GM 360 PRO
380-400-415 V AC Three-phase with neutral (4 wire)
96A
150A
± 20% @ 100% load
-40% +20% @50% load
Programmable from 1 to 125 sec. at steps of 1 sec
380/400/415 V AC three-phase with neutral (4 wire)
87A
60kVA
54kW
1.5 x In for t > 500ms
± 3% resistive load
≤ 1% with linear load
≤ 3% with distorted load
103% Infinite, 110% 10 min, 125% 1 min
110% Infinite,125% 60 minutes, 150% 10 minutes
GM 380 PRO
50-60Hz
125A
200A
± 20%
40-72Hz
(2)
THDi = 2,5%
≥ 0.99
50/60Hz
116A
80kVA
72kW
0.9
± 1%
± 0.5%
(6)
≤ 3,5% with distorted load
3:1
0.01%
±240Vdc
10A (20A optional)
GM 3100 PRO
155A
250A
145A
100kVA
90kW
≤ 1% with linear load