Status / Alarm Codes - GMP GM 360 PRO Manual Del Usario

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

S
/
TATUS
ALARM CODES
Using a sophisticated self-diagnosis system, the UPS is able to check and signal its own status and any anomalies or faults
which may occur during normal operation. If there is a problem, the UPS signals the event by showing the code and the type of
active alarm on the display.
STATUS: indicates current UPS status.
CODE
S01
S02
S03
S04
S05
S06
S07
S08
S09
S10
S11
S12
S13
COMMAND: indicates presence of an active command.
CODE
C01
C02
C03
C04
C05
C06
C07
C08
WARNING: these messages relate to a special UPS configuration or operation.
CODE
W01
W02
W03
W04
W05
104
DESCRIPTION
Pre-loading in progress
Load not powered (stand-by status)
Start-up phase
Load powered by bypass line
Load powered by inverter
Battery operating mode
Waiting for battery charging
Economy mode on
Ready for start-up
UPS locked – load not powered
UPS locked – load on bypass
BOOST stage or battery charger locked – load not powered
Frequency converter - load powered by inverter
DESCRIPTION
Remote power-off command
Remote load command on bypass
Remote power-on command
Battery test in progress
Manual bypass command
Emergency power-off command
Remote battery charger power-off command
Load command on bypass
DESCRIPTION
Low battery warning
Programmed shutdown on
Programmed shutdown imminent
Bypass disabled
Synchronization disabled (UPS in Free running)
Tabla de contenido
loading

Este manual también es adecuado para:

Gm 380 proGm 3100 pro

Tabla de contenido