24 Vdc CONTROL UNIT FOR SLIDING GATES
OPERATING INSTRUCTIONS – INSTALLATION INSTRUCTIONS
This 24Vdc control unit for sliding gates offers high performance and a wide range of adjustments, with opening and
closing slow-downs, encoder management and the possibility of managing both opening and closing travel limit
devices.
If correctly installed, thanks to encoder control, this control unit guarantees installation conforming to current safety
regulations.
A sophisticated electronic control monitors the power circuit at all times and disables the control unit in the event of
malfunctions that could impair efficiency of the electronic clutch.
The parameter settings and the operating logics are shown on a handy LCD display, which indicates gate status during
normal operation. Operating times are controlled by self-learning during programming.
In "C" version gearmotors, the control unit is on board the gearmotor. A waterproof enclosure is available for housing
the control unit and any buffer batteries (optional) which must correspond to the indications in the following table.
Supply voltage of transformer
Supply voltage of control unit
Absorbed power
Motor max. load
Accessories max. load
Flashing lamp/courtesy light max. load
Operating ambient temperature
Protection fuses
Function logics
Opening / closing time
Pause time
Thrust force
Slow-downs
Terminal board inputs
Radio connector
Terminal board outputs
Board dimensions
Characteristics of 230Vac toroidal transformer
Characteristics of 115Vac toroidal transformer
Characteristics of optional batteries
Characteristics of outdoor grade enclosure
Different output values can be obtained on the 24Vac output depending on the mains voltage value. Before
start-up, always check the transformer output voltage. It must not exceed 26Vac for both power feed values of
230Vac and 5Vac. Voltage must be measured load free, i.e. with the transformer powered and disconnected
from the board.
To ensure people's safety, all warnings and instructions in this booklet must be carefully observed. Incorrect
installation or incorrect use of the product could cause serious harm to people.
Keep the instructions for future reference
Make sure there is an adequate differential switch upstream of the system as specified by current laws, and install a
single-pole thermal breaker on the electrical power mains.
To lay cables, use adequate rigid and/or flexible tubes.
Always separate connection cables of low voltage accessories from those supplying 115/230 Vac. To prevent any
interference whatever, use separate sheaths.
If you wish to put the control unit in a remote position with respect to the motor, the maximum length of the
power cables between the control unit and the motor must not exceed 3 m, using cables with a diameter
of 2.5 mm
for the motor and 3x0.5 mm
2
guarantee correct encoder operation for distances longer than 3 meters.
Procedure for securing components inside the water-tight enclosure, refer to paragraph 15.

. GENERAL CHARACTERISTICS

2. TECHNICAL SPECIFICATIONS

Automatic / Step-by-step automatic/Semi-automatic /
24 Vac power supply, Supply to batteries, Encoder, Total
opening, Pedestrian opening, Opening safety devices,
Closing safety devices, Stop, Opening travel limit devices,
24Vdc supply for accessories, 24Vdc for motors, Courtesy
light/ Flashing lamp 24 Vdc, Electrical lock 12 Vdc/ac
3. PREPARATIONS
for the encoder and the travel limit devices (optionals). One cannot
2
4
230/115 Vac (+6 -10%) - 50/60 Hz.
24 Vac (+6 -10%) - 50/60 Hz.
3 W
70 W
24Vdc 500mA
24Vdc 15W max.
-20°C +50°C
4 (3 self resetting)
Step-by step semi-automatic/Condominium
Through self-learning during programming
Through self-learning during programming
Four levels adjustable on display
At opening and closing
Closing travel limit devices
Rapid 5 pin connector for receiver
145 x 128 mm.
primary 230Vac sec. 22Vac 120VA
primary 115Vac sec. 20Vac 120 VA
12V 4Ah dimensions: 90 x 70 x 108 mm
306 x 225 x 130 mm. - IP55