Activate the System

You have completed your Quantum system
installation. For onsite factory startup, call Lutron
Technical Support and select Startup to schedule a
field service visit. Allow for 10 working days between
day of call and scheduled visit.
In the U.S., Canada, and the Caribbean: 1.800.523.9466
In Mexico: 888.235.2910
In Europe: +44.207.702.0657
In Asia: +65.6220.4666
In Japan: +81.355.758.411
In all other countries: +1.610.282.6701
14 Quantum
Light Management Hub
TM
LNK
LNK
LNK
PWR
PWR
PWR
OK
OK
OK
H/L H/L N N
ERR
EMG
BUS
ERR
EMG
BUS
STAT
ERR
EMG
BUS
V
ERR
EMG
BUS
STAT
V
PWR
E2
E2
E1
E1
E2
E2
E1
E1
L2
L1
L2 Tx Rx
L2 Heartbeat
L1 Tx Rx
L1 Heartbeat
Processor Tx Rx
Processor Heartbeat
Error
Power
LED
Normal
Operation
Power Supply
LNK PWR
On
OK
Bus Supply
ERR /
Off
EMG
BUS
Flash* or
Off
STAT
Steady
flash
V
PWR
On
Processor
L1/L2
Off
Tx Rx
No links
L1/L2
Flashing
Heartbeat
No links
PWR
L1/L2
Flashing
Tx Rx
with link
L1/L2
Flashing
Heartbeat
with link
Processor
Off
Tx Rx
Processor
Flashing
Heartbeat
Error
Off
Power
On
* If the bus supply ERR/EMG and BUS LEDs are both flashing
in unison, the bus supply is in boot mode.
Problem
Probable Cause and
Indicator
Solution
Off
No power from
transformer: Check
that power feed and
power switch are on
On
Emergency contact
closure is active
Steady
Miswire detected on
flash*
corresponding bus:
Check wiring
On
Unit fault or debug
mode: Check to see if
bus supply is in debug
mode
Off
No power or unit fault
On
Unit fault
Off
No power
Off
Link error: Run
software diagnostics
Off
Link error: Run
software diagnostics
Off
Link error: Run
software diagnostics
Off
Link error: Run
software diagnostics
On
Software uploading
Flashing
Boot mode
Flashing
Boot mode (if Tx Rx
also flashing)
On
Link error: Run
software diagnostics
Off
Check power supply