S F E - E V
6 DIAGNOSTIC MODE
The SFE-EV controller features a diagnostic mode, where the service data and historic are stored and
displayed. These data can be helpful for troubleshooting in case of system dysfonctionement.
To access the diagnostic mode, press and hold the UP arrow for 5 seconds. Once in diagnostic mode, press the
regeneration button to scroll from one parameter to the next one.
Data
1
xxxx
2
SAxx
3
FFxx
4
Lxxxxxx
E
5
Hxxxxx
N
6
LHxxxx
G
7
Xx:xx
L
Π xx
I
S
H
8
A xx
S xx
9
- xx
10
dΠ xx
11
E:xx
12
Xx:xx
Π xx
13
A xx
S xx
14
- xx
15
dΠ xx
16
E:xx
17
Xx:xx
Π xx
18
A xx
S xx
19
- xx
20
dΠ xx
21
E:xx
22
AAA.Y
End
Description
Number of regenerations carried out.
Number of regenerations remaining before triggering the salt alarm.
Number of days elapsed since the last regeneration.
*1
Litres treated.
*1
Number of hours elapsed since first installation.
*1
Average consumption since first installation.
Time and date of last regeneration. When this data is displayed, the first and second sector light up.
01
The last regeneration was launched in instantaneous manual mode
02
The last regeneration was launched in delayed manual mode at the programmed time
01
Automatic regeneration launched in timed mode (SH:01)
02
Automatic regeneration launched in combined mode (SH:02) because volume exhausted.
Automatic regeneration launched in combined mode (SH:02) because maximum number of days for obligatory
03
regeneration has been reached
Automatic regeneration launched in combined mode (SH:02) because maximum number of days between
04
regenerations calculated by the controller based on the number of users has been reached
05
Automatic regeneration launched in volume mode (SH:03)
Automatic regeneration launched in volume mode (SH:03) because maximum number of days for obligatory
06
regeneration has been reached
Automatic regeneration launched in volume mode (SH:03) because maximum number of days between
07
regenerations calculated by the controller based on the number of users has been reached
08
Automatic regeneration launched in interval mode (SH:04)
09
Regeneration started after Holiday
01
Regeneration started instantaneously by remote start
02
Regeneration started at programmed time by remote delayed start
Number of days elapsed since the second last regeneration
Number of days elapsed since the latest meter pulse.
Optimisation of latest regeneration brine (in percentage).
Time and date of penultimate regeneration. When this data is displayed, the third and fourth sector light up.
01 / 02
01/.../09
Same parameters as point 8, but referring to penultimate regeneration
01 / 02
Number of days elapsed since third to last regeneration.
Number of days elapsed since the latest meter pulse.
Optimisation of penultimate regeneration brine (in percentage).
Time and date of third to last regeneration. When this data is displayed, the fifth and sixth sector light up.
01 / 02
01/.../09
Same parameters as point 8, but referring to third from last regeneration
01 / 02
Number of days elapsed since fourth to last regeneration.
Number of days elapsed since the latest meter pulse.
Optimisation of third to last regeneration brine (in percentage).
Software version and revision.