S F E - E V
DATA
E
N
G
L
I
S
H
DESCRIPTION
SH: Regeneration Mode:
- 1: Time clock regeneration on predefined days
- 2: Volumetric delayed regeneration
- 3: Volumetric immediate regeneration
- 4: Regeneration are initiated based upon a programmed time interval (every 2, 3,
4, 6, 8 or 12 hours). The first generation starts at the regeneration time set in the
basic menu and following regeneration will be carried out depending on the
programmed interval.
Days enabled for regeneration. Display shows "dx y" where x represents the day of
the week (1-7) and y indicates whether the selected day is enabled for regeneration
"1" or disabled "0". On the upper part of the display, enabled days are on while
disabled days are not displayed.
To change the setting of the selected day (x) =
To enable or disable the selected day (y) press
The option is displayed and programable only if SH: 1.
Variable brining function: on or off. This parameter can be used to enable the variable
brining function, if the function is enabled the brine tank will be filled for brine
preparation before regeneration. To change the value, use the
Refill first option. This option can be used to set the brine tank refill cycle before (0)
or after (1) each regeneration. To change the value, use the
The option is displayed only if ub is set to OFF.
Interval between regenerations in hours. To change, use the
The option is displayed only if SH: 4.
Inlet water hardness. Enter hardness of water at inlet in French degrees (°f) or
german degrees (°d).
To change press
or
.
The option is displayed only if SH: 2 or SH: 3.
50
DEFAULT
2
All enabled
ON
buttons.
0
keys.
2
keys.
MIN -MAX
1-4
N.A.
ON – OFF
0 – 1
2 – 12