More Detail on Adjusting Output Signal at Zero Velocity
In certain cases, the remote display will not read the same as the transducer
display output at zero velocity. To correct this discrepancy you will need to
adjust the output signal at zero velocity. Put the transducer into setup mode
and sequence through the setup messages until "AdJUSt ZErO" is shown on
the display. The transducer then displays and outputs the voltage or current
that has been set as the zero value. Adjust the transducer output voltage or
current using the  and  pushbuttons. Adjust the output signal until the
remote device displays the expected zero. The transducer displays the
voltage or current that corresponds to the factory calibration. The velocity
readings should now be the same on both the setup/troubleshooting display
and the remote display.
Davantage de Détails Sur le Réglage du Signal de sortie à une Vitesse
Nulle
Dans certains cas, il se peut qu'un affichage à distance ne corresponde pas à
la sortie du transducteur à vitesse nulle. Pour corriger cette différence, il est
nécessaire de régler le signal de sortie à vitesse nulle. Pour ce faire, mettre le
transducteur en mode de configuration et défiler à travers les messages de
configuration jusqu'à l'apparition de "AdJUSt ZErO" à l'écran. Le
transducteur affiche et émet alors la tension ou l'intensité réglée à la valeur
zéro. Régler la tension ou l'intensité de sortie du transducteur à l'aide des
boutons poussoirs  et . Régler le signal de sortie jusqu'à ce que l'appareil
à distance affiche le zéro nécessaire. Le transducteur affiche la tension ou
l'intensité correspondant à la calibration en usine. Les mesures de vitesse
doivent désormais être identiques sur l'affichage de configuration/dépannage
et sur celui à distance.