All loads are bound to all buttons and the dimmer paddle on the LMSW-105-CCT.
To change the recorded CCT levels for any button, simply adjust the lights in the room to the desired levels and
then press and hold the desired button for 5 seconds.
The percent corresponds to a CCT value of Max-Min * %.
Load Selection Procedure
A configuration button allows access to our patented Push n' Learn™ technology to change the binding relationship between control
devices and loads.
Step 1 Enter Push n' Learn
1. Using a pointed tool, press and hold the configuration button for 3 seconds, until the Red LED on the switch
begins to blink.
2. When you release the configuration button, the red LED on other communicating DLM Local Network
devices begins to blink rapidly.
3. The DLM Local Network is now in PnL mode. The Red LEDs continue to blink until you exit PnL mode.
4. All loads in the room turn OFF after entering PnL. After one second, one load turns ON. This is Load #1,
which is bound to the LMSW-105-CCT paddle and all buttons as part of the Plug n' Go factory default
setting. The Blue LED will be ON bright for all switch buttons, dimmers, scene buttons and sensors that are
bound to this load.
Step 2 Load selection
1. Press and release the configuration button to step through the loads connected to the DLM Local Network.
As each load turns ON note which devices (dimmers, scene and switch buttons and sensors) are showing
the blue LED. These devices are currently bound to the load that is ON.
2. To unbind a button from a load, press the button while its blue LED is ON. The blue LED turns OFF to indicate
the button no longer controls the load that is currently ON. On the scene switch, unbinding a load from a scene
button removes it from the scene so that when the scene activates the load's state does not change.
3. Pressing the switch button again while the load is ON rebinds the load to the button and the blue LED
illuminates.
Step 3 Exit Push n' Learn
1. Press and hold the configuration button until the red LED turns off, approximately 3 seconds.
CAUTION: TO CONNECT A COMPUTER TO THE DLM LOCAL NETWORK USE THE LMCI-100.
Loads do not operate as expected.
Switch button or rocker
paddle LEDs don't light
The wrong lights are
controlled
Button or rocker paddle
doesn't actuate
LEDs turn ON and OFF
but load doesn't switch
PLUG N' GO OPERATION (PNG)
UNIT ADJUSTMENT - PUSH N' LEARN (PNL)
TROUBLESHOOTING
NEVER CONNECT THE DLM LOCAL NETWORK TO AN ETHERNET PORT –
IT MAY DAMAGE COMPUTERS AND OTHER CONNECTED EQUIPMENT.
1. Check to see that the the switch is connected to the DLM Local Network.
2. Check for 24VDC input to the switch: Plug in a different DLM device at the switch location. If the
device does not power up, 24VDC is not present.
• Check the high voltage connections to the room controller.
• If high voltage connections are good and high voltage is present, recheck DLM Local Network
connections between the switch and the room controller.
1. Configure the switch buttons to control the desired lights using the Push n' Learn adjustment
procedure.
1. Make sure the switch frame and button are assembled properly.
2. Make sure that the wall plate is not pinching the frame.
1. Make sure device is not in PnL.
2. Check load connections to room controller.
2
Default CCT
level
100%K
75%K
50%K
25%K
loading