Rockwell Automation Allen-Bradley PowerFlex 40 Guia De Inicio Rapido página 19

Ocultar thumbs Ver también para Allen-Bradley PowerFlex 40:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 93
See the PowerFlex 40 User Manual for more information on parameters.
No.
Parameter
A065 [Analog Out Sel]
Option
Output Range
0 "OutFreq 0-10"
0-10V
1 "OutCurr 0-10"
0-10V
2 "OutVolt 0-10"
0-10V
3 "OutPowr 0-10"
0-10V
4 "TstData 0-10"
0-10V
5 "OutFreq 0-20"
0-20 mA
6 "OutCurr 0-20"
0-20 mA
7 "OutVolt 0-20"
0-20 mA
8 "OutPowr 0-20"
0-20 mA
9 "TstData 0-20"
0-20 mA
10 "OutFreq 4-20"
4-20 mA
11 "OutCurr 4-20"
4-20 mA
12 "OutVolt 4-20"
4-20 mA
13 "OutPowr 4-20"
4-20 mA
14 "TstData 4-20"
4-20 mA
15 "OutTorq 0-10"
0-10V
16 "OutTorq 0-20"
0-20 mA
17 "OutTorq 4-20"
4-20 mA
18 "Setpnt 0-10"
0-10V
19 "Setpnt 0-20"
0-20 mA
20 "Setpnt 4-20"
4-20 mA
21 "MinFreq 0-10"
0-10V
22 "MinFreq 0-20"
0-20 mA
23 "MinFreq 4-20"
4-20 mA
A066 [Analog Out High]
A067 [Accel Time 2]
A068 [Decel Time 2]
A069 [Internal Freq]
(1)
A070
[Preset Freq 0]
A071
[Preset Freq 1]
A072
[Preset Freq 2]
A073
[Preset Freq 3]
A074
[Preset Freq 4]
A075
[Preset Freq 5]
A076
[Preset Freq 6]
A077
[Preset Freq 7]
(1)
To activate [Preset Freq 0] set P038 [Speed Reference] to option 4.
Input State
Input State
of Digital In 1
of Digital In 2
(I/O Terminal 05)
(I/O Terminal 06)
0
1
0
1
0
1
0
1
(2)
When a Digital Input is set to "Accel 2 & Decel 2", and the input is active, that input overrides the settings in this table.
A078 [Jog Frequency]
A079 [Jog Accel/Decel]
A080 [DC Brake Time]
A setting of 99.9 Secs = Continuous
A081 [DC Brake Level]
A082 [DB Resistor Sel]
A083 [S Curve %]
Min/Max
Display/Options
0/23
1
Minimum Output Value
0V = 0 Hz
0V = 0 Amps
0V = 0 Volts
0V = 0 kW
0V = 0000
0 mA = 0 Hz
0 mA = 0 Amps
0 mA = 0 Volts
0 mA = 0 kW
0 mA = 0000
4 mA = 0 Hz
4 mA = 0 Amps
4 mA = 0 Volts
4 mA = 0 kW
4 mA = 0000
0V = 0 Amps
0 mA = 0 Amps
4 mA = 0 Amps
0V = 0%
0 mA = 0%
4 mA = 0%
0V = Min. Freq
0 mA = Min. Freq
4 mA = Min. Freq
0/800%
1%
0.0/600.0 Secs
0.1 Secs
0.1/600.0 Secs
0.1 Secs
0.0/400.0 Hz
0.1 Hz
0.0/400.0 Hz
0.1 Hz
Input State
of Digital In 3
Frequency Source
(I/O Terminal 07)
0
0
0
0
1
0
1
0
0
1
0
1
1
1
1
1
0.0/[Maximum Freq]
0.1 Hz
0.1/600.0 Secs
0.1 Secs
0.0/99.9 Secs
0.1 Secs
0.0/(Drive Amps × 1.8) 0.1 Amps
0/99
0 = "Disabled"
1 = "Normal RA Res"
0/100%
1%
Maximum Output Value
[Analog Out High]
P035 [Maximum Freq]
200% Drive Rated FLA
120% Drive Rated Output Volts
200% Drive Rated Power
65535 (Hex FFFF)
P035 [Maximum Freq]
200% Drive Rated FLA
120% Drive Rated Output Volts
200% Drive Rated Power
65535 (Hex FFFF)
P035 [Maximum Freq]
200% Drive Rated FLA
120% Drive Rated Output Volts
200% Drive Rated Power
65535 (Hex FFFF)
200% Drive Rated FLA
200% Drive Rated FLA
200% Drive Rated FLA
100.0% Setpoint Setting
100.0% Setpoint Setting
100.0% Setpoint Setting
P035 [Maximum Freq]
P035 [Maximum Freq]
P035 [Maximum Freq]
Accel / Decel Parameter Used
[Preset Freq 0]
[Accel Time 1] / [Decel Time 1]
[Preset Freq 1]
[Accel Time 1] / [Decel Time 1]
[Preset Freq 2]
[Accel Time 2] / [Decel Time 2]
[Preset Freq 3]
[Accel Time 2] / [Decel Time 2]
[Preset Freq 4]
[Accel Time 1] / [Decel Time 1]
[Preset Freq 5]
[Accel Time 1] / [Decel Time 1]
[Preset Freq 6]
[Accel Time 2] / [Decel Time 2]
[Preset Freq 7]
[Accel Time 2] / [Decel Time 2]
2 = "NoProtection"
3-99 = % of Duty Cycle
English-17
Default
0
DIP Switch Position
0-10V
0-10V
0-10V
0-10V
0-10V
0-20 mA
0-20 mA
0-20 mA
0-20 mA
0-20 mA
0-20 mA
0-20 mA
0-20 mA
0-20 mA
0-20 mA
0-10V
0-20 mA
0-20 mA
0-10V
0-20 mA
0-20 mA
0-10V
0-20 mA
0-20 mA
100%
20.0 Secs
20.0 Secs
0.0 Hz (for IP66,
NEMA/UL Type
4X drives)
60.0 Hz (for
IP20 drives)
0.0 Hz
5.0 Hz
10.0 Hz
20.0 Hz
30.0 Hz
40.0 Hz
50.0 Hz
60.0 Hz
(2)
10.0 Hz
10.0 Secs
0.0 Secs
Amps × 0.05
0
0% (Disabled)
Tabla de contenido
loading

Este manual también es adecuado para:

Allen-bradley frn 5 serieAllen-bradley frn 6 serie

Tabla de contenido