English-16
Advanced Group Parameters
No.
Parameter
A051
[Digital In1 Sel]
I/O Terminal 05
A052
[Digital In2 Sel]
I/O Terminal 06
A053
[Digital In3 Sel]
I/O Terminal 07
A054
[Digital In4 Sel]
I/O Terminal 08
(1)
Important: Speed source for IP66, NEMA/
UL Type 4X rated drives comes from A069
[Internal Freq].
A055 [Relay Out Sel]
A056 [Relay Out Level]
A058
[Opto Out1 Sel]
A061
[Opto Out2 Sel]
A059
[Opto Out1 Level]
A062
[Opto Out2 Level]
A055, A058 & A061 Setting
6
7
8
10
16
17
18
20
23
A064 [Opto Out Logic]
A064 Option
Opto Out1 Logic
0
NO (Normally Open)
1
NC (Normally Closed)
2
NO (Normally Open)
3
NC (Normally Closed)
See the PowerFlex 40 User Manual for more information on parameters.
Min/Max
Display/Options
0/27
0 = "Not Used"
1 = "Acc & Dec 2"
2 = "Jog"
3 = "Aux Fault"
4 = "Preset Freq"
5 = "Local"
6 = "Comm Port"
7 = "Clear Fault"
8 = "RampStop,CF"
9 = "CoastStop,CF"
10 = "DCInjStop,CF"
11 = "Jog Forward"
12 = "Jog Reverse"
13 = "10V In Ctrl"
0/24
0 = "Ready/Fault"
1 = "At Frequency"
2 = "MotorRunning"
3 = "Reverse"
4 = "Motor Overld"
5 = "Ramp Reg"
6 = "Above Freq"
7 = "Above Cur"
8 = "Above DCVolt"
9 = "Retries Exst"
10 = "Above Anlg V"
11 = "Logic In 1"
12 = "Logic In 2"
0.0/9999
0.1
0/24
See A055 for Options.
0.0/9999
0.1
A056, A059 & A062 Min/Max
0/400 Hz
0/180%
0/815 Volts
0/100%
0.1/9999 Secs
1/9999 Counts
1/180 degs
0/1
0/400 Hz
0/3
1
Opto Out2 Logic
NO (Normally Open)
NO (Normally Open)
NC (Normally Closed)
NC (Normally Closed)
14 = "20mA In Ctrl"
15 = "PID Disable"
16 = "MOP Up"
17 = "MOP Down"
18 = "Timer Start"
(1)
19 = "Counter In"
20 = "Reset Timer"
21 = "Reset Countr"
22 = "Rset Tim&Cnt"
23 = "Logic In1"
24 = "Logic In2"
25 = "Current Lmt2"
26 = "Anlg Invert"
27 = "EM Brk Rlse"
13 = "Logic 1 & 2"
14 = "Logic 1 or 2"
15 = "StpLogic Out"
16 = "Timer Out"
17 = "Counter Out"
18 = "Above PF Ang"
19 = "Anlg In Loss"
20 = "ParamControl"
21 = "NonRec Fault"
22 = "EM Brk Cntrl"
23 = "Above Fcmd"
24 = "MsgControl" (for
FRN 6.01 and later)
Default
4
4
5
11
0
0.0
2
1
0.0
0