English-14
Display Group Parameters
No.
Parameter
d001 [Output Freq]
d002 [Commanded Freq]
d003 [Output Current]
d004 [Output Voltage]
d005 [DC Bus Voltage]
d006 [Drive Status]
d007-
[Fault x Code]
d009
d010 [Process Display]
d012 [Control Source]
d013 [Contrl In Status]
d014 [Dig In Status]
d015 [Comm Status]
d016 [Control SW Ver]
d017 [Drive Type]
d018 [Elapsed Run Time]
d019 [Testpoint Data]
d020 [Analog In 0-10V]
d021 [Analog In 4-20mA]
d022 [Output Power]
d023 [Output Powr Fctr]
d024 [Drive Temp]
d025 [Counter Status]
d026 [Timer Status]
d028 [Stp Logic Status]
d029 [Torque Current]
Smart Start-Up with Basic Program Group Parameters
The PowerFlex 40 is designed so that start up is simple and efficient. The Program Group
contains the most commonly used parameters.
= Stop drive before changing this parameter.
No.
Parameter
P031 [Motor NP Volts]
Set to the motor nameplate rated volts.
P032 [Motor NP Hertz]
Set to the motor nameplate rated frequency.
P033 [Motor OL Current]
Set to the maximum allowable motor current.
P034 [Minimum Freq]
Sets the lowest frequency the drive will output
continuously.
P035 [Maximum Freq]
Sets the highest frequency the drive will output.
P036 [Start Source]
Sets the control scheme used to start the drive.
(1)
When active, the Reverse key is also active
unless disabled by A095 [Reverse Disable].
See the PowerFlex 40 User Manual for more information on parameters.
Min/Max
Display/Options
0.0/[Maximum Freq]
0.1 Hz
0.0/[Maximum Freq]
0.1 Hz
0.00/(Drive Amps × 2)
0.01 Amps
0/Drive Rated Volts
1 VAC
Based on Drive Rating
1 VDC
0/1 (1 = Condition True)
Bit 3
Decelerating
F2/F122
F1
0.00/9999
0.01 – 1
0/9
Digit 1 = Speed Command
(See P038; 9 = "Jog Freq")
0/1 (1 = Input Present)
Bit 3
DB Trans On
0/1 (1 = Input Present)
Bit 3
Digital In 4
0/1 (1 = Condition True)
Bit 3
Comm Error
1.00/99.99
0.01
1001/9999
1
0/9999 Hrs
1 = 10 Hrs
0/FFFF
1 Hex
0.0/100.0%
0.1%
0.0/100.0%
0.1%
0.00/(Drive Power × 2)
0.01 kW
0.0/180.0 deg
0.1 deg
0/120 degC
1 degC
0/9999
1
0.0/9999 Secs
0.1 Secs
0/7
1
0.00/(Drive Amps × 2)
0.01 Amps
Min/Max
Display/Options
20/Drive Rated Volts
1 VAC
15/400 Hz
1 Hz
0.0/(Drive Rated Amps× 2) 0.1 Amps
0.0/400.0 Hz
0.1 Hz
0/400 Hz
1 Hz
0/6
0 = "Keypad"
1 = "3-Wire"
2 = "2-Wire"
3 = "2-W Lvl Sens"
4 = "2-W Hi Speed"
5 = "Comm Port"
6 = "Momt FWD/REV"
Bit 2
Bit 1
Accelerating
Forward
Digit 0 = Start Command
(See P036; 9 = "Jog")
Bit 2
Bit 1
Stop Input
Dir/REV In
Bit 2
Bit 1
Digital In 3
Digital In 2
Bit 2
Bit 1
DSI Option
Transmitting
Default
Based on Drive Rating
60 Hz
Based on Drive Rating
0.0 Hz
60 Hz
(1)
0
Bit 0
Running
Bit 0
Start/FWD In
Bit 0
Digital In 1
Bit 0
Receiving
Tabla de contenido