Bosch FLM-420-I8R1-S Guia De Instalacion página 15

Ocultar thumbs Ver también para FLM-420-I8R1-S:
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 17
FLM-420-I8R1-S Octo-input Interface Module with Relay
F
i
NOTICE! Installation must only be performed by authorized and specialized personnel!
!
WARNING! Live components and stripped cable! Risk of injury from electric shock. The
system must be current-free during connection work.
CAUTION! Electrostatic discharge (ESD)! Electronic components could become damaged.
Ground yourself using a wrist strap or take other suitable actions.
Functional description
The FLM-420-I8R1-S Octo-input Interface Module provides two monitoring functions (see Section 5. , page 5):
1.
Monitoring a line with EOL resistor for standby or triggering (interruption/short circuit)
2.
Monitoring a potential free contact for "open" and "closed" states
The monitoring functions of the eight inputs can be selected individually by setting the corresponding addresses.
Additionally, the FLM-420-I8R1-S has a change-over contact relay to provide a potential free output contact.
The programming is carried out via the programming software of the fire panel.
Cables are fed through rubber bushings or PG cable glands (see Section 3. , page 4).
The pluggable terminal blocks of the interface module allow for an easy wiring (even if built in).
Address setting
Fit a rotary switch in the required position using a pan head slotted screwdriver (see Section 4. , page 5).
It is not permitted to use different operating modes in the same loop, stub or T-tap next to each other!
Address (A)
Operating mode
0 0 0
Loop/stub in LSN improved version mode with automatic addressing
0 0 1 ... 2 5 4
Loop/stub/T-taps in LSN improved version mode with manual addressing
CL 0 0
Loop/stub in LSN classic mode (address range: max. 127)
2 5 5 ... 2 9 9
Non-permitted address range (error message on fire panel)!
Connection (see Section 6. , page 6)
Description
+U | 0V
LSN
a1- | b1+
LSN
SHIELD
+U | 0V
LSN
a2- | b2+
IN
1 ... 8: + | -
REL
NC | COM | COM | NO
NOTICE!
The maximum cable length of all inputs connected to the loop or stub is 500 m in total.
Additionally, all outputs which are not electrically isolated from LSN must be included in the
i
total line length calculation (e.g. peripherals connected via C points).
The activation of the inputs IN 1...8 has to be carried out electrically isolated from LSN (e. g.
with relay contact, pushbutton, etc.).
The inputs must have a minimum activation time of 3.2 s.
Bosch Sicherheitssysteme GmbH
Function
Auxiliary power supply (support points to loop through)
LSN incoming
Cable shielding (if present)
Auxiliary power supply (support points to loop through)
LSN outgoing
Input 1 to Input 8
Change-over relay (NC contact/COM, COM/NO contact)
Installation guide
| en
15
F.01U.032.847 | 3.0 | 2008.10