Error Messages - ABB RVC Instrucciones De Instalación Y De Funcionamiento

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 34

ERROR MESSAGES

Description
F1
Current too small.
F2
Phase not found
after 10 trials.
Load is varying too quickly.
F3
Phase error:
closest value is 0°.
The controller could not find
a known configuration.
F4
---closest value is 30°.---
F5
---closest value is 60°.---
F6
---closest value is 90°.---
F7
---closest value is 120°.---
F8
---closest value is 150°.---
F9
---closest value is 180°.---
F10 ---closest value is 210°.---
F11 ---closest value is 240°.---
F12 ---closest value is 270°.---
F13 ---closest value is 300°.---
F14 ---closest value is 330°.---
F15 C/k not found after 10 trials.
The load is varying too
quickly.
F16 C/k too small (< 0.01).
Step size too small
or CT too big.
F17 C/k too high (> 3.00).
Step size too big
or CT too small.
F18 Sequence not found after
10 trials. The load is varying
too quickly.
F19 Unknown sequence. The
controller could not find a
known sequence.
Recommended action
Check that the CT short-circuit is
removed and re-start AUTO SET.
Re-start AUTO SET procedure
under more stable conditions.
Check connections,
capacitors and fuses.
------
------
------
------
------
------
------
------
------
------
------
Re-start AUTO SET procedure
under more stable conditions.
Adapt the step size or the CT
ratio.
Adapt the step size or the CT
ratio.
Re-start AUTO SET procedure
under more stable conditions.
Check connections,
capacitors and fuses.
11
Tabla de contenido
loading

Tabla de contenido