4
Technical data
General data and operating conditions
Protection of persons and devices
Enclosure
Insulation resistance
Insulation of control
circuits
Short−circuit strength
Discharge current
Cyclic mains switching
Mounting conditions
Mounting place
Mounting position
Clearance
above/beneath
at the side
Connection conditions for DC power supply module
AC mains operation
DC−bus operation
50
EN 60529
IP 20
NEMA 250
Protection against contact in
accordance with type 1
EN 61800−5−1
Overvoltage category III
from 2000 m amsl: external measures for complying with
the overvoltage category II are required, e.g.
l
connecting isolating transformer upstream
l
connecting overvoltage protection system upstream
EN 61800−5−1
up to 2000 m amsl:
Safe mains isolation by double/reinforced insulation for
mains with neutral earthing with a rated voltage for the
external conductor/star point up to 300 V.
from 2000 m amsl:
If an overvoltage protection system is connected upstream,
additional external separating measures are required for
maintaining the safe mains isolation.
EN 61800−5−1
DC−bus connection: Not short−circuit−proof
Brake resistor connection: without restrictions
Control connections: without restrictions
EN 61800−5−1
> 3.5 mA
Cyclic mains switching of 5 times in 5 minutes is permissible
without restrictions.
in the control cabinet
vertical
Comply with the device−relating mounting instructions.
Can be installed in a row without any clearance
Direct connection
Direct connection of axis modules via terminals or busbar
system
More information can be found in the Hardware Manual,
chapter "DC−bus operation".
l
Not in the wire range of
the lower terminals
Observe regulations and
safety instructions!
EDK94PNE245 DE/EN/FR/ES/IT 4.0