DIEL ME 100 Manual De Instalacion Y Uso página 16

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

ENGLISH
• ME100:
F=0, P=140, A=160, L=90, H=100, t=0, d=25, S=5, U=0
• ME100 V3: F=0, P=140, A=160, L=90, H=100, t=0, d=25, S=9, U=1
Anyway, the necessary time for programming is checked.
Over 1 minute from beginning of the programming phase, the same is interrupted
and not saved so the previous set limits remain active. At the end of programming
the new data will be saved in memory, the device executes a display test and the
system is prearranged in automatic way and visualises the maximum measured
temperature and the relative channel.
DATA VISUALIZATION
Referring to F it is possible to show all parameters of interest by buttons UP/DOWN.
To show one specific parameter, or one specific measure of temperature, select it
and push the button AUTO/MANUAL, the MANUAL led turns on to flag a manual
status mode. To return to the normal automatic mode push again AUTO/MANUAL
button.
During automatic working the higher temperature and the relative number of
channels appear on the display. To visualize the maximum values of the machine
push and hold the buttons AUTO/MANUAL and ENTER/TEST at the same time.
The visualisation of the maximum temperatures is signalised through the T MAX –
PROGRAM led which is placed on the front-end panel.
With the buttons UP/DOWN it is possible to see the historical maximum
temperature achieved by all active channels. For exit push button AUTO/MANUAL.
Please note that the maximum values are reset every time you confirm a new
program sequence.
ASCII PROTOCOL (ME 100)
Sending to the "serial gate" the following string "$XX#YY"<CR >< LF> where XX
(01-99) it is the address of the device and YY (01-10) is the code of data request,
the communication starts. The commands from 01 to 10 respectively assume the
following meaning: reading current temperature, maximum historical, thresholds of
pre alarm, thresholds of alarm, thresholds turning off fan, thresholds lighting fan,
state of activation channels, state of activation fan, state of probes, general state
of device.
- 16 -