Fully illustrated step by step instructions are
downloadable on www.saniflo.co.uk
1
WARNING NOTICE
SANICOM
®
is a lifting pump for wastewater used in commercial
applications (restaurants, hairdressing salons, the catering
industry etc.). The unit operates automatically, has a high
performance level, and is safe and reliable, provided all the
rules for installation and maintenance in this notice are
strictly followed.
Especially those indicated by:
"
" Failure to comply with this instruction could endanger
the safety of persons,
"
" Indication that a risk of electrical
origin exists,
"
" Electrical installation must be carried out by a
professional electrician.
"ATTENTION" Failure to comply with this instruction could
endanger the safe functioning of the apparatus.
For any additional information, please contact our customer
service department.
HOW IT WORKS
SANICOM
®
contains 1 pump. The tank is equipped with a
sensor tube which controls the automatic activation of the motor
when waste enters the unit.
As soon as the waste enters the tank, the pump starts.
2
LIST OF PARTS SUPPLIED
3
DIMENSIONS
4
SANICOM
®
TECHNICAL DATA AND APPLICATION
Application
Type
Maximum vertical pumping height
Voltage
Frequency
Maximum power consumption
Maximum current consumption
Electrical class
Protection index
Max temp with intermittent functioning
Net weight
* In the case of bath or shower tray, make sure the waste traps
are raised 15 cm above floor level.
CAUTION: 1. All applications other than those described in
this notice are prohibited.
2. Do not exceed an incoming flow rate greater
than 80% of the flow rate stated on the design
curve
5
in any of the apparatus.
5
PERFORMANCE CURVES
6
VERTICAL/HORIZONTAL PUMPING
7
INSTALLATION
The pump has securing devices, preventing it from turning
or moving.
7a
FITTING
1- Warning: The space in which SANICOM
be large enough to leave at least 600mm around the unit for
easy maintenance. This space must be well lit, ventilated,
and must never be immersed in water and must be
protected from frost.
Sinks, washing machine,
dishwasher or shower*
or bath*
FF03-P95
8 m
220 – 240 V
50 Hz
750 W
3.3 A
I
IP44
90°
10 kg
®
is installed must
2- Isolation valves should be fitted to the inlet pipework and
discharge pipework to isolate the unit in case of the need
for service.
3- This evacuation pipe must be designed so as to prevent
back-flow from the sewers.
7b
CONNECTION TO SIDE INLETS
Use the flexible inlet connector
Using a metalwork saw, saw the desired input point, remove
any burrs and then fix the flexible inlet connector with the
D
jubilee clip
.
CAUTION:
In the case of an installation for drainage of
greasy wastes allow for a grease trap in front of each input
point.
Connection to the inlet can be made using a DN40
or DN50 pipe. To make a DN50 connection, cut off the end
A
of sleeve
beforehand.
7c
CONNECTION TO SANITARY WARE
To connect bathtub (or shower), make sure the waste trap
height is raised by at least 19 cm above floor level.
Connection must be made using 40 mm or 50 mm diameter
pipework, with minimum slope of 1%.
7d
CONNECTION TO SOIL AND VENT PIPE OR DRAIN
The disposal of waste from the SANICOM
through a 32 mm diameter copper or plastic pipes (or PVC,
ABS, etc.).
Horizontal discharge pipework should maintain a 1% fall
(1cm/M) to the soil and vent pipe. If a vertical rise is
required, this must be installed at the start of the run,
before the horizontal section.
Take care that the discharge valve flap faces the direction
of flow.
If the end of the discharge pipework is much lower than the
unit, install a riser pipe about 80mm long from the highest
point of the discharge run and fit an air admittance pipe on
top (capable of withstanding at least 15psi pressure.) to
break the syphon.
End the outlet pipe at the waste stack.
7e
IN CASE SERVICE IS NEEDED
Allow for a drain-off point at the bottom of the rising waste
pipe. Ensure that the unit is easily accessible for possible
maintenance.
7f
ELECTRICAL CONNECTION
The electrical installation should be carried by a qualified
person.
All wiring must conform to BS7671, 1992 requirements for
electrical installation. The unit requires a 220/240 V single
phase AC 50 Hz supply (UK specification). Do not connect the
unit to a conventional plug and socket. The unit should be
connected to a fully earthed electrical supply (class 1). It must
be wired into an unswitched fused fixed wiring connector
protected by a 10 amp fuse and a residual current detector
(30 mA). This connection must be used exclusively for
supplying the SANICOM unit.
The wires in the mains lead are coloured in accordance with
the following code:
Brown
-
Blue
-
Green/Yellow
-
WARNING: Ensure the electricity is turned OFF at the main
switch board before wiring to connector. All work on cable,
pressure chamber and motor should only be carried out by a
qualified SANIFLO servicing agent, as special tools are
required.
CAUTION:
When the apparatus is connected up for the first
time, it will work for 5 seconds even if there is no water in
the basin. This operation acts as a manual start-up.
A
for side input connections.
®
can discharged
Live
Neutral
Earth