Ground fixation
Sizes 80 to 300 V
Top view of FRAME
Sizes 702 to 1100 V
Top view of FRAME
It is possible to fix the frame to the ground (mounts with bolts not supplied by CIAT), strength to be defined as a function of the
unit's weight and centre of gravity.

Evaporator limits

The curves below represent the minimum and maximum permitted temperature differences for chilled or glycol solution as a
function of the outlet temperature.
Brazed plate
evaporator
Minimum / maximum flow
The flow in the exchangers must always be between the minimum and maximum values below.
Sizes
80
90
100
MINI m
3
/h
2.9
MAXI m
3
/h
6.7
7.4
9.0
Hydraulic
module
Sizes
180 to
300
Water outlet temperature ˚C
120
150
180
200
240
3.6
5.1
5.8
6.9
7.8
10.0
13.1
15.4
17.6
20.4
Sizes
80 - 300
350 to 500
540 to 700
702 to 1100
ΔT used for the calculation of the performance tables
Glycol solution
Example above: For a water outlet: + 7°C
ΔT minimum: 2.8°C / Water regime: 9.8 / 7°C
ΔT maximum: 6.5°C / Water regime: 13.5 / 7°C
In the case of temperature differences outside of the two curves, please consult
us.
300
350
400
500
540
10.4
11.7
13.3
17.3
18.1
24.5
30.7
34.6
41.9
45.9
33
Sizes 350 to 700 V
Top view of FRAME
LD - LDC - LDH
ILD - ILDC - ILDH
L1
L2
L3
L4
316
316
1988
1044
281
281
2185
2123
281
281
2735
2123
987
986
3684
2125
800
900
600
700
702
20.8
20.8
22.1
24.4
29.3
50.7
69.5
77
50.7
63.2
1000 1100
31.6
34
77
77
Tabla de contenido