Wherever anti-freeze is required, use anti-freeze fluids with specific protective
agents, as set out on standard UNI 8065.
In the event of installations on pre-existing systems, these must be equipped
with a magnetic cleansing filter with a filtration capacity of no less than 500
microns and a magnetic field of no less than 10,000 Gauss (e.g. IDRAMAG F).
This should be installed on the circuit and sized according to the capacity of the
circulation pump.
For installations on new systems, as an alternative to the system mentioned
above, you can also install magnetic cleansing filters with a magnetic capacity
of no less than 1,000 Gauss (e.g. IDRAMAG or IDRAMAG FS). These should
be installed on a branch with a draining capacity of approximately 10% of the
system's total flow rate.
In both cases, you must ensure that the fluid has been treated with suitable
protective agents, as set out in standard UNI 8065.
Any damage caused by solid, fibrous or abrasive substances that cannot be
attributed to a defect in the original product, will INVALIDATE THE WARRANTY.

3.3 TEMPERATURES AND AMBIENT HUMIDITY

Ambient temperature
[°C]
Up to 25
30
35
40
• The medium temperature must be higher or the same as ambient
• Operation outside recommended conditions may shorten pump
• Operation at edge conditions can shorten pump lifespan.
16
Permitted ambient and media temperature
Medium temperature [°C]
min
-10
-10
-10
-10
temperature so that the condensate doesn't gather on pump
surfaces.
lifetime and could void the warranty.
Relative ambient
max
110
100
90
80
humidity
< 95%