Check that the battery terminals have been inserted correctly.
Otherwise the SPS NET could be damaged.
The SPS NET should be charged every six months if it is
not in use.
Fig. A

8. TROUBLESHOOTING.

Use the following table to resolve minor problems:
Issue
Red LED On.
The battery backup time
is much shorter than the
rated value.
No output and no LED
indicators lit.

9. SPECIFICATIONS.

AC INPUT
Voltage
Frequency
Efficiency
Overload protection
BATTERY INPUT
Battery type
Rated voltage
1.3 Ah
Capacity
(2600 mAh)
Back-up time
Overload voltage
Overload recovery voltage
Battery undervoltage
Efficiency
No-load consumption
Leakage current when OFF
Cold start function
14
Fig. B
Possible causes
Solutions
Overload or short-circuit
Press the button
on the SPS NET, has
during more than 1
switched to fault mode.
second and release it
to reset the unit.
Battery charge too low.
Contact your
distributor to replace
the special battery.
Internal failure.
Contact your
distributor.
90 V AC ~ 264 V AC
50 Hz ~ 60 Hz
> 81% (Rated load R,
battery charged)
Yes
Output < 11.7 V for 10 s. in line mode
Lithium-Ion
3.7 V DC
3 PCS
7800 mAh
> 120 min. @ standard router
4.5 V DC
4.2 V DC
3.0 V DC
> 75%
<0.8 W
< 10 uA
Yes
DC OUTPUT
Voltage
Rated power
Maximum power
Transfer time
Output short-circuit protection
Overload protection
CHARGER OUTPUT
Charging method
Charging voltage
Charging current
Typical recharge time
FUNCTION BUTTON
ON/ OFF button
GENERAL
Maximum altitude
Relative humidity
Temperature
Storage Temp.
STANDARDS
Safety
Electromagnetic compatibility
(EMC)
Safety and Environmental
Management
PHYSICAL
Mains input
Output cable
Dimensions D x W x H (mm)
Net weight (kg)
Table 2. General technical specifications.
12 V DC ± 5%
12 W ( 1 A)
25 W (2.1 A)
0 ms.
Yes (output < 5 V for 3 ms.)
Yes
Output < 11.4 V for 10 s.
Output < 10.8 V for 0.4 s
DC - CV
(constant voltage with current
limiting)
4.2 V ± 0.05 V DC
1.6 A @ 25 ºC
4.5 hours to 90% capacity
Connects and disconnects the
SPS NET
2400 masl
Up to 90 % non-condensing.
0 ~ 40 ºC.
-15 ºC ~ 60 ºC.
EN62368-1
EN55032: Class A
EN61000-3-2
EN61000-3-3
EN55035
ISO 9001 and ISO 14001.
2-Pin Schuko cable
1 m. (DC male jack, OD 5.5 mm.,
ID 2.5 mm.* 2 PCS)
2 PCS DC jack 2.5 mm. to 2.1 mm.
150 x 80 x 40
332 g
SALICRU