PROBLEM
THE DISPLAY SHOWS
C01
THE DISPLAY SHOWS
C02
THE DISPLAY SHOWS
ONE OR MORE OF THE
FOLLOWING CODES:
A30, A32, A33, A34
AND THE UPS WILL NOT
START
THE DISPLAY SHOWS
ONE OR MORE OF THE
FOLLOWING CODES:
F09, F10
THE DISPLAY SHOWS
ONE OR MORE OF THE
FOLLOWING CODES:
F11, F14, F15, F16, F17,
L06, L07, L08, L09, L14,
L15, L16, L17, L18, L19,
L20, L21, L22
THE DISPLAY SHOWS
ONE OR MORE OF THE
FOLLOWING CODES:
F03, F04, F05, A08, A09,
A10
THE DISPLAY SHOWS
ONE OR MORE OF THE
FOLLOWING CODES:
F42, F43, F44, L42, L43,
L44
IV330 Rev.001 SIEL S.p.A.
Data di emissione: 2011-09-28
POSSIBLE CAUSE
THE JUMPER IS MISSING
FROM THE R.E.P.O.
CONNECTOR (J13, REF. 15 -
"VIEW OF THE UPS
CONNECTIONS") OR IS NOT
INSERTED CORRECTLY
MAINTENANCE BYPASS
ISOLATOR (SWMB) CLOSED
THE JUMPER IS MISSING
FROM THE TERMINALS FOR
THE REMOTE MAINTENANCE
BYPASS (J10, REF. 17 - "VIEW
OF THE UPS CONNECTIONS")
AMBIENT TEMPERATURE
< 0°C
FAULT IN TEMPERATURE
PROBE ON HEAT SINK
FAULT IN THE INPUT STAGE
OF THE UPS
PHASE 1 HAS A VOLTAGE
MUCH LOWER THAN THE
OTHER TWO PHASES.
FAULTY LOADS APPLIED
FAULT IN THE INPUT OR
OUTPUT STAGE OF THE UPS
NO CONNECTION ON ONE
OR MORE PHASES
INTERNAL PROTECTIVE
FUSES BLOWN ON THE
PHASES OR INPUT RELAY
BROKEN
THE INTERNAL PROTECTION
FUSES ON THE BATTERIES
HAVE BLOWN
SOLUTION
Assemble the jumper or check that it is inserted
correctly.
Open the isolator (SWMB) situated behind the door.
Insert the jumper
Heat
the
environment,
temperature to rise above 0°C and then start up the
UPS
Activate the maintenance bypass (SWMB), turn the
UPS off and on again and exclude the maintenance
bypass. If the problem persists, call your local service
centre
Activate the maintenance bypass (SWMB), turn the
UPS off and on again. Exclude the maintenance
bypass. If the problem persists, call your local service
centre
Open SWIN, turn the UPS from the battery, wait for the
end of the sequence and close SWIN
Remove the load. Insert the maintenance bypass
(SWMB), and turn the UPS off and then on again.
Exclude the maintenance bypass. If the problem
persists, call your local service centre
Activate the maintenance bypass (SWMB) and turn the
UPS off and then on again. Exclude the maintenance
bypass. If the problem persists, call your local service
centre
Check the connections to the terminals
Call your local service centre
Call the nearest service centre.
wait
for
the
heat
sink
Pag. 94 di 252 + FR