The table below shows the sizes of the isolators of the UPS and the sizes of the battery fuses (SWBATT): these devices
are accessible from the front of the UPS.
There are also indications about the internal fuses (not accessible) protecting the input and output lines and the
maximum input and rated output currents. To install the UPS, see the block diagram in the "USE" section of the
"Description" paragraph.
Fuses are to be replaced with ones of the same size and the characteristics indicated in the table below.
UPS
Non-automatic switches
mod.
UPS input /
[kVA]
Separate bypass
SWIN / SWBYP
(optional)
10
40A(4P)
15
63A(4P)
20
63A(4P)
*
The
max.
input
and a battery charger charged with 4A.
** In versions with additional internal battery chargers (optional), the maximum input current on lines L2 and L3 must be
increased by 7A.
SHORT CIRCUIT
If a failure occurs on the load, the UPS protects itself by limiting the value and duration of the current output (short-circuit
current). These values also depend on the operating status of the UPS at the time of the failure; there are two different
cases:
UPS in NORMAL OPERATION: the load is switched instantaneously to the bypass line (I
line is connected to the output without any internal protection (blocked after t>0.5s)
UPS in BATTERY OPERATION: the UPS protects itself by providing a current equivalent to about 1.5 times the
rated current for 0.5s and turns itself off after this time has elapsed
BACKFEED
The UPS has internal protection against backfeed through metal separating devices.
There is an output on the relay board (optional) for activating a releasing device to be installed upstream from the UPS.
The UPS has an internal device (redundant bypass power supply) which, when a failure occurs on the
machine, activates the bypass automatically, thus keeping the load powered without any internal protection
and without any limitation to the power supplied to the load.
Under these emergency conditions, any disturbance present on the input line will affect the load.
See also the "USE" section of the "Redundant Auxiliary Power Supply for Automatic Bypass" paragraph.
IV330 Rev.001 SIEL S.p.A.
Data di emissione: 2011-09-28
D
EVICES OF THE
Isolators and internal protective devices
UPS output /
Rectifier input
Maintenance
SWOUT / SWMB
25A FF 500V
40A(4P)
63A(4P)
500V (6.3x32)
63A(4P)
500V (6.3x32)
current
refers
to
a
rated
UPS
Fuses
Battery fuse
fuse
SWBATT
32A gG 400V
(6.3x32)
(10x38)
2 x 20A FF
50A gG 400V
(14x51)
2 x 20A FF
50A gG 400V
(14x51)
load
(PF
=
0.9)
Input
Output fuse
current
[A] **
*
Max
25A FF 500V
20A
(6.3x32)
2 x 20A FF
29A
500V (6.3x32)
2 x 20A FF
38A
500V (6.3x32)
and
an
input
voltage
2
2
t=11250A
s): the input
Pag. 69 di 252 + FR
Output
current
[A]
Rated
15A
22A
29A
of
346V,