FUNCTION
Bypass Synchronization
speed
External synchronization
External temperature
Bypass mode
Bypass active in stand-by
Bypass frequency tolerance
Bypass min.-max. threshold
Eco mode sensibility
Eco mode
min.-max. threshold
UPS without battery
Battery low time
Automatic battery test
Parallel common battery
Internal battery capacity
External battery capacity
Battery charging algorithm
Battery recharging current
IV330 Rev.001 SIEL S.p.A.
Data di emissione: 2011-09-28
DESCRIPTION
Selects the synchronisation speed of the inverter to the
bypass line
Selects the source of synchronisation for the inverter
output
Activates reading of the external temperature probe
Selects the mode of use of the bypass line
Load supply from bypass with UPS in stand-by
Selects the accepted range for the input frequency for
switching to the bypass and for the synchronisation of the
output
Selects the accepted voltage range for switching to the
bypass
Selects the intervention sensitivity during operation in ECO
mode
Selects the accepted voltage range for operation in ECO
mode
Operating mode without batteries (for converters or voltage
stabilizers)
Estimated autonomy time remaining for "battery low"
warning
Interval of time for the automatic battery test
Common Battery for parallel UPS systems
Nominal Battery capacity for internal batteries
Nominal Battery capacity for external batteries
Algorithm and Battery recharging threshold
Recharging current compare to battery nominal capacity
DEFAULT
1 Hz/sec
From bypass line
Disable
Enabled /
High sensitivity
Disable (load NOT
supplied)
± 5%
Low: 180V
High: 264V
Normal
Low: 200V
High: 253V
Operating with
Batteries
3 min.
40 ore
Disable
Change according
with UPS model
7Ah for UPS without
internal batteries;
0Ah all other cases
Two levels
12%
Pag. 88 di 252 + FR