The Regard 2400/2410 Device Menu; The Menu Structure - Dräger REGARD 2400 Instrucciones De Uso

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 67

The REGARD 2400/2410 device menu

11
The REGARD 2400/2410 device menu
The REGARD 2400/2410 has an internal device menu to configure and read out the settings.
Via the menu the REGARD 2400/2410 switches to the Inhibit mode and bridges the average
determination (both restricted to 20 minutes).
Average values: The average values are the result of 16 measurements in the configured time
between 1 and 254 seconds (16 seconds to 1:07 hours altogether). When all 16 measurements
are over the alarm threshold or the range is 16 times higher than the alarm threshold, an alarm
is triggered.
11.1

The menu structure

The menu can be called up by pressing the F1 and F2 keys. It is divided into various functions.
There are 6 different menu items which display information, freeze the REGARD 2400/2410 in
its current status or put it into test mode. Each function automatically returns to measuring mode
after 20 seconds.
Some of these items are protected by the password 1875.
INHI:
Inhibit mode, all the relays are frozen in their current status for a period of
20 minutes. Password-protected menu item
MOFF:
Average determination off ("TÜV" (Technical Inspection Service) function). Average
determination is frozen for the next 20 minutes. Password-protected menu item.
TOUT:
Testing the output relays. Password-protected menu item.
SOFT:
Display of the device software version.
MOD:
Display of internal communication details such as address (MADR),
Serial Communication (MCON) and Baud Rate (MBAU).
LOG:
Display of logger status.
In order to access the items listed, the keys F1, F2 or F1+F2 (together) must be activated.
48
Dräger REGARD 2400/2410
Tabla de contenido
loading

Este manual también es adecuado para:

Regard 2410

Tabla de contenido