coNNec
R 0%
R 100%
UNit
DisP.lo
DisP.Hi
NeW.Pas
9116 UNiVeRsal coNVeRteR
selected sensor connection type for RtD or linear resistance
measurements (for seNsoR = Ni or Pt or iN.tYPe = liN.R):
2W = 2-wire
3W = 3-wire
4W = 4-wire
if 2W or 3W is selected, the end user must ensure that the
applied sensor wiring does not introduce failures exceeding the
requirements for the safety application.
0% input range for linear resistance measurements
(for iN.tYPe = liN.R).
this value must be < (R 100% - minimum span), refer to 4.2.1
100% input range for linear resistance measurements
(for iN.tYPe = liN.R)
this value must be > (R 0% + minimum span), refer to 4.2.1
selected temperature unit for iN.tYPe = teMP
°c = degrees celsius
°F = degrees Fahrenheit
For iN.tYPe ≠ teMP selectable units refer to routing diagram
0% display value on 4501. can be used as base for relay
setpoints (for iN.tYPe ≠ teMP)
100% display value on 4501. can be used as base for relay
setpoints (for iN.tYPe ≠ teMP)
Password for protection of the device configuration from
unauthorized access. Range from 0 to 9999.
Version No. V2R0
safety Manual
13