LERBAKKEN 10, 8410 ROENDE DENMARK
Module 9116B1
Terminal 51-52, 51-53
Ui
30 V
Ii
120 mA
Pi
900 mW
Ci
3 nF
Li
1 μH
Module 9116B1
Terminal 51-54, 52-54
Uo
28 V
Io
93 mA
Po
650 mW
Module 9116B1
Terminal 51-53
Uo
28 V
Io
1.1 mA
Po
8 mW
Module 9116B1
Terminal 51-52
Uo
8.3 V
Io
0.2 mA
Po
0.4 mW
Module 9116B1
Terminal 41,42,43,44
Uo
8.3 V
Io
13.1 mA
Po
27.3 mW
Installation notes:
For installation in Zone 2, the module must be installed in an outer enclosure having an IP protection
of at least IP54 according to type of protection Ex-n or Ex-e.
For installation on Power Rail in Zone 2, only Power Rail type 9400 supplied by Power Control Unit
type 9410 is allowed.
In type of protection "intrinsic safety iD" the parameters for intrinsic safety for gas group IIB are
applicable.
Do not separate connectors when energized and an explosive gas mixture is present.
Do not mount or remove modules from the Power Rail when an explosive gas mixture is present.
If the sensor circuits or loop supply circuits have been installed in a type of protection other than
"Intrinsic Safety", the module shall not be reinstalled in type of protection "Intrinsic Safety"
Revision date:
2010-02-12
34
Group
Co
Lo
IIC
80 nF
4 mH
IIB
640 nF
16 mH 218 μH/Ω
IIA
2.1 μF
32 mH 436 μH/Ω
Group
Co
Lo
IIC
80 nF 1000 mH
IIB
640 nF 1000 mH 17 mH/Ω
IIA
2.1 μF 1000 mH 35 mH/Ω
Group
Co
Lo
IIC
7 μF 1000 mH 100 mH/Ω
IIB
73 μF 1000 mH 400 mH/Ω
IIA
1000 μF 1000 mH 800 mH/Ω
Group
Co
Lo
IIC
7 μF
207 mH
IIB
73 μF
828 mH
IIA
1000 μF 1000 mH 10 mH/Ω
Version Revision
V5 R0
9116 - Product Version 9116-002
Module 9116B2
Terminal 51-52, 51-53
Ui
30 V
Ii
120 mA
Pi
900 mW
Ci
3 nF
Li
1 μH
Module 9116B2
Lo/Ro
Terminal 51-54, 52-54
54 μH/Ω
Uo
21.4 V
Io
93 mA
Po
650 mW
Module 9116B2
Lo/Ro
Terminal 51-53
4 mH/Ω
Uo
21.4 V
Io
1.1 mA
Po
8 mW
Module 9116B2
Lo/Ro
Terminal 51-52
Uo
8.3 V
Io
0.2 mA
Po
0.4 mW
Module 9116B2
Lo/Ro
Terminal 41,42,43,44
1 mH/Ω
Uo
8.3 V
5 mH/Ω
Io
13.1 mA
Po
27.3 mW
Prepared by:
9116QI01
Group
Co
Lo
IIC
0.16 μF
4 mH
IIB
1.13 μF
16 mH 218 μH/Ω
IIA
4.15 μF
32 mH 436 μH/Ω
Group
Co
Lo
IIC
0.16 μF 1000 mH
IIB
1.13 μF 1000 mH 17 mH/Ω
IIA
4.15 μF 1000 mH 35 mH/Ω
Group
Co
Lo
IIC
7 μF 1000 mH 100 mH/Ω
IIB
73 μF 1000 mH 400 mH/Ω
IIA
1000 μF 1000 mH 800 mH/Ω
Group
Co
Lo
IIC
7 μF
207 mH
IIB
73 μF
828 mH
IIA
1000 μF 1000 mH 10 mH/Ω
PB
Lo/Ro
54 μH/Ω
Lo/Ro
4 mH/Ω
Lo/Ro
Lo/Ro
1 mH/Ω
5 mH/Ω
Page: