40
CARACTÉRISTIQUES TECHNIQUES
TECHNICAL CHARACTERISTICS - TECHNISCHE DATEN - CARATTERISTICHE TECNICHE -
TECHNISCHE EIGENSCHAPPEN - CARACTERÍSTICAS TÉCNICAS - CARACTERÍSTICAS TÉCNICAS
EN
COMPLIANCE
SYSTEM CONNECTION
Supply types / number of wires
Management
Frequency
SUPPLY
CONSUMPTION
Supply
Current circuit
CURRENT (TRMS)
Starting current (Ist)
Minimum current (Imin)
Transition current (Itr)
Reference current (Iref)
Permanent overload (Imax)
Short-term over-current
VOLTAGE (TRMS)
Specified operating scope
Extended operating scope
POWERS
Active
Reactive
Resolution
ENERGY
Active
Reactive
Total and partial metering
Bidirectional metering (EA+ and EA-)
Resolution
ACCURACY
Active energy
TARIFFS
Tariff management
Number of tariffs managed
Tariff exchange input
METROLOGICAL LED
Impulse weight
Colour
DISPLAY
Type
Refresh time
Back-lighting illumination time
List of functions displayed
* Functions available only via communication, the complete list of these functions
is given in the downloadable M-BUS communication table.
COUNTIS E36 - Ref.: 540 684 D
European EMC Directive No. 2004/108/EC (15/12/2004)
LV Directive No. 2006/95/EC Dated 12 December 2006
MID Directive 2004/22/EC
EN50470-1/-3 (February 2007)
Three phase 4 wires 3 x 230/400 V
Single phase 2 wires 230 V
Three phase 3 wires 3x230 V / 3x400 V
Detection of cabling error
IEC: 50/60 Hz ± 5 Hz / MID: 50 Hz ± 1 Hz
Autosupplied
< 10 VA or 2 W
< 2.5 VA
80 mA
0.5 A
2 A
20 A
100 A
3000 A for 10 ms (EN50470-3 and IEC 62053-21)
230 V AC Phase/Neutral 400 V AC Phase/Phase +/10%
230 / 400 V AC + 15%
Yes
No*
0.1 kW
Yes
No*
Total only (0 to 9999999 kWh)
No
1 kWh
Class B (EN 50470-3)
Yes*
4*
No*
500 impulses / kWh or 2 Wh / impulse
Red
7 Digit LED with blue back-lighting
1 s
30 s
Cf. table below