LEVEL 3 CONTINUED
Function
Options
rEu.d
Select output modes: Direct/Reverse
Caution: Settings affect fail safe state.
[1r.2d]
1d.2d
1r.2r
1d.2r
Select Reverse on SP1 for heating and Direct for
cooling applications.
rEu.L
Select SP1/2 LED indicator modes
[1n.2n]
1i.2n
1n.2i
1i.2i
SPAn [0.0]
to ±25% sensor maximum
Sensor span adjust
For recalibrating to align readings with another instrument e.g. External Meter, data logger .
See Full Operating Manual (ADV ANCED SETTINGS).
ZEro
[0.0]
to ±25% sensor f/s
Zero sensor error (see Sensor span adjust above).
ChEK
[oFF]
on
Select control accuracy monitor
rEAD
[Var]
hi
Lo
Read control accuracy monitor
tECh
[Ct A]
CT b Ct 1 Ct 2 Ct 3 Ct 4 oS 1 uS oS 2
Read Autotune tuning cycle data (see Operating Manual)
Software version number
UEr
rSET
[nonE]
ALL
Resets all functions to factory settings
Caution: This selection will lose all of the current settings.
[Factory settings] shown in brackets
SP1
SP2
Reverse
Direct
Direct
Direct
Reverse
Reverse
Direct
Reverse
SP1
SP2
Normal
Normal
Invert
Normal
Normal
Invert
Invert
Invert
-1999–2500 in Linear
-1999–2500 in Linear
Will be affected by dECP settings in Level A
LEVEL 4
LEVL 4
Access to level 4 is gained through UEr in level 3. Press and hold
Enter level 4 at Lock , release
and
together . Display reads LoCK nonE
Program security using Lock [nonE]
Select from three Lock options: Press and hold
locks level 3, 4, A (and C when fitted)
LEV.3
locks level 2, 3, 4, A (and C when fitted)
LEV.2
locks all functions (including C when fitted)
ALL
Any locked functions and options can still be read.
Note:
Press
to access following functions.
Function
Options
ProG [Auto]
StAY
Program mode auto-exit switch
Auto-exit returns display to normal if 60 seconds of key inactivity, select StAY to disable
no.AL [oFF]
on
Disable SP2 alarm annunciator -AL-
Select on to disable -AL-
di.SS dir
1 to 32
Display sensitivity
dir = direct display of input 1 = maximum, 32 = minimum sensitivity
dEr.S
0.1 to 1.0
Derivative sensitivity
Remember next menu exit point and use as new
SEt.L (oFF)
on
menu entry point, except when exit is in Level 1.
LEVEL P
See PROGRAMMER Section, page 11.
LEVL P
LEVEL C
COMMSSETTINGS; visible only when Comms option
LEVL C
fitted.
Additional in depth information on controller operation is available in the APPGUIDE.PDF
available for down load from www .cal-controls.com
and
for 10 seconds.
, press
to index.
[Factory settings] shown in brackets
[6]
[0.5]
9