Settings [Factory settings] shown in brackets
Function
Press
or
to change
Event output
E.oP
To Return to:
Press and hold
LEVL P
To Read % Programmer memory used:
Press
and
together in LEVL P / ProG 1
USEd
1–100%
Press
or
to change
Function can be applied to each
[nonE]
segment independently to trigger
an output at the start of that
segment for the duration of that
segment. Setting blocked unless
either or both outputs SP2A or
SP3A have been configured as an
Event Output in Level 2 or Level A
respectively .
SP2A de-energised to mark event
2d
SP2A energised to mark event
2E
SP3A de-energised to mark event
3d
SP3A energised to mark event
3E
SP2A and SP3A de-energised to
2d.3d
mark event
SP2A energised SP3A de-energised
2E.3d
to mark event
SP2A and SP3A energised to mark
2E.3E
event
SP2A de-energised SP3A energised
2d.3E
to mark event
Memory Allocation Table
Segment type
Memory required
Ramp
4 Bytes
Ramp with Holdback
5 Bytes
Soak
2 Bytes
Step
3 Bytes
Loops (1–3)
1 Byte
Loops (4+)
2 Bytes
Call
1 Byte
Event Output
1 Byte
Program Header
1 Byte
Maximum capacity:
351 Bytes
31 Programs
126 Segments
Examples:
1. 1 program of 58 Ramps and 58 Soaks
2. 4 programs of 14 Ramps and 14 Soaks
3. 31 programs of 2 Ramps and 1 Soak
4. 2 programs of 10 Ramps, 10 Soaks, 2 Steps and 1 loop
Memory Full Indication
Should the programmer memory capacity be reached during program configuration, the
display will show 'FULL '
349 Bytes
340 Bytes
341 Bytes
136 Bytes
17