4. Electrical work
SW2-1~8 SW3-1~3 Fixed set temperature with DIP switch of FTC (Available when SW1-6 is ON)
SW2-1~3 Fixed set temperature for Heating mode (Table 1~2 depends on SW1-7,8.)
SW2-1
SW2-2
SW2-3
Table1
OFF
OFF
OFF
25 ºC
ON
OFF
OFF
30 ºC
OFF
ON
OFF
35 ºC
ON
ON
OFF
40 ºC
OFF
OFF
ON
45 ºC
ON
OFF
ON
50 ºC
OFF
ON
ON
55 ºC
ON
ON
ON
60 ºC *1
The selectable temperature range for Heating mode depends on outdoor unit type.
*1 Do not use this setting when you use the standard outdoor unit without a plate HEX (refrigerant-water) inside.
SW2-4~6 Fixed set temperature for Hot Water mode (Table 1~2 depends on SW1-7,8.)
SW2-4
SW2-5
SW2-6
Table1
OFF
OFF
OFF
46 ºC
ON
OFF
OFF
48 ºC
OFF
ON
OFF
50 ºC
ON
ON
OFF
52 ºC
OFF
OFF
ON
54 ºC
ON
OFF
ON
56 ºC
OFF
ON
ON
58 ºC
ON
ON
ON
60 ºC *1
The selectable temperature range for Hot Water mode depends on outdoor unit type.
*1 Do not use this setting when you use the standard outdoor unit without a plate HEX (refrigerant-water) inside.
SW2-7,8 Fixed set temperature for Anti-freeze mode (Table 1~2 depends on SW1-7,8.)
SW2-7
SW2-8
Table1
OFF
OFF
5 ºC
ON
OFF
10 ºC
OFF
ON
15 ºC
ON
ON
20 ºC
SW3-1~3 Fixed set temperature for Cooling mode (Table 1~2 depends on SW1-7,8.)
SW3-1
SW3-2
SW3-3
Table1
OFF
OFF
OFF
7 ºC
ON
OFF
OFF
10 ºC
OFF
ON
OFF
12 ºC
ON
ON
OFF
15 ºC
OFF
OFF
ON
18 ºC
ON
OFF
ON
20 ºC
OFF
ON
ON
22 ºC
ON
ON
ON
25 ºC
4.5. Connecting external input
FTC can be operated by following external input.
4.5.1 EXTERNAL INPUT ( Contact signal )
TB142
OFF
1-2
(IN1)
3-4
(IN2)
5-6
(IN3)
Normal
Forced Comp. OFF
7-8
(IN4)
OFF
10-11
(COM-IN5)
OFF
10-12
(COM-IN6)
OFF
10-13
(COM-IN7)
OFF
10-14
(COM-IN8)
OFF
*1 Heating ECO mode sets the set temperature depending on the outdoor temperature.
Table2
25 ºC
30 ºC
35 ºC
40 ºC
45 ºC
50 ºC
55 ºC
60 ºC *1
Table2
25 ºC
30 ºC
35 ºC
40 ºC
45 ºC
50 ºC
55 ºC
60 ºC *1
Table2
5 ºC
10 ºC
15 ºC
20 ºC
Table2
7 ºC
10 ºC
12 ºC
15 ºC
18 ºC
20 ºC
22 ºC
25 ºC
ON
Remark
Not in use
Not in use
Forced Comp. OFF
SW3-6=OFF
Normal
SW3-6=ON
Cooling
Heating
Heating ECO *1
Hot Water
Anti-Freeze
TB142
2
4
6
8
10
12
1
3
5
7
9
11
13
At site
FTC
1
2
3
4
5
Forced Comp. OFF →
6
7
Cooling
8
9
10
Heating
11
HeatingECO →
12
Hot Water
13
Anti-Freeze →
14
TB142
14
11
Tabla de contenido