Pt100/1000 Inputs - Grundfos CRE Instrucciones De Instalación Y Operación

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Sensor function/measured parameter
"Inlet pressure"
"Diff. press., inlet"
"Discharge press."
"Diff. press.,outlet"
"Diff. press, pump"
"Press. 1, external"
"Press. 2, external"
"Diff. press., ext."
"Storage tank level"
"Feed tank level"
"Pump flow"
"Flow, external"
"Liquid temp."
"Temperature 1"
"Temperature 2"
"Diff. temp., ext."
"Ambient temp."
"Other parameter"
"Unit"
Parameter
Possible units
Pressure
"bar", "m", "kPa", "psi", "ft"
Level
"m", "ft", "in"
Pump flow
"m³/h", "l/s", "yd³/h", "gpm"
Liquid temperature
"°C", "°F"
Other parameter
"%"
"Electrical signal"
Select signal type:
"0.5-3.5 V"
"0-5 V"
"0-10 V"
"0-20 mA"
"4-20 mA".
Sensor range, minimum value
Set the minimum value of the connected sensor.
Sensor range, maximum value
Set the maximum value of the connected sensor.
Factory setting
data. "Limit 2 exceeded"
See section
10. Technical

7.6 "Pt100/1000 inputs"

Pos.
Available inputs depend on the functional module fitted in the
1
pump:
2
3
Function (terminal)
4
"Pt100/1000 input 1, setup"
5
(17 and 18)
6
"Pt100/1000 input 2, setup"
7
(18 and 19)
8
* See section
9
If you want to set the Pt100/1000 input for a feedback sensor, we
10
recommend that you do this via the "Assisted pump setup" menu.
See section
11
If you want to set a Pt100/1000 input for other purposes, you can
12
do this manually.
13
You can set the analog inputs via the "Setup, analog input" menu.
14
See section
15
If you make the manual setting via Grundfos GO, you need to
16
enter the menu for the Pt100/1000 input under the "Settings"
menu.
Not shown
Function
Not shown
The Pt100/1000 inputs can be set to these functions:
"Not active"
"Feedback sensor"
The sensor is used for the selected control mode.
"Ext. setpoint infl."
See section
"Other function".
Measured parameter
Select one of the parameters listed below, i.e. the parameter to
be measured in the system by the PT100/1000 sensor connected
to the actual PT100/1000 input. See fig. 54.
Fig. 54 Overview of PT100/1000 sensor locations
Parameter
"Liquid temp."
"Temperature 1"
"Temperature 2"
"Ambient temp."
Measuring range
-50 to 204 °C.
Factory setting
See section
FM 200*
(standard)
-
-
5.2.1 Identification of functional
7.41 "Assisted pump
setup".
7.42 "Setup, analog
input".
7.13 "External setpoint
function".
1
2
TT
TT
4
DTT
10. Technical
data.
FM 300*
(advanced)
module.
3
TT
Pos.
1
2
3
Not shown