USING THE LASER WITH ACCESSORIES
The laser is equipped with a 1/4" x 20 female thread on the bottom of the unit. This thread is to
accommodate current or future D
WALT accessories. Only use D
E
for use with this product. Follow the directions included with the accessory.
CAUTION: The use of any other accessory not recommended for use with this tool could be
hazardous.
If you need any assistance in locating any accessory, please contact D
Co., 701 East Joppa Road, Baltimore, MD 21286 or call 1-800-4-D
See our catalog on the World Wide Web at www.dewalt.com.
LEVELING THE LASER
To manually level this tool, secure the laser to the leveling base provided and adjust the leveling
knobs (D) until the bubbles in the vials (E) are centered.
MAINTENANCE
To maintain the accuracy of your work, check the laser often to make sure it is properly
calibrated. See Field Calibration Check.
Calibration checks and other maintenance repairs may be performed by D
centers.
When not in use, store the laser in a safe place. Do not store your laser at temperatures below
-5˚F (-20˚C) or above 140˚F (60˚C).
Do not store your laser when wet. The laser should be dried first with a soft dry cloth.
Cleaning
Exterior plastic parts may be cleaned with a damp cloth. Although these parts are solvent resis-
tant, NEVER use solvents. Use a soft dry cloth to remove moisture from the tool before storage.
Field Calibration Check
CHECKING ACCURACY – LEVEL (FIG. 3–6)
Checking the level accuracy of the laser unit requires two parallel walls at least 25' (7.7m) apart.
It is important to conduct a calibration check using a distance no shorter than the distance of the
applications for which the tool will be used.
1. Place the unit 2"–3" (5–8cm) from the first wall, facing the wall (Fig. 3).
2. Level the laser unit as necessary to center the bubble vials (E).
3. Mark the beam position (a) on the first wall.
4. Turn the unit 180° and level the laser unit.
5. Mark the beam position (b) on the second wall (Fig. 4).
6. Place the unit 2"–3" (5–8cm) from the second wall, facing the wall (Fig. 5).
7. Adjust the height and level the laser until the beam hits the mark at position (b).
8. Turn the unit 180° and aim the beam near the mark on the first wall from Step 3 (Fig. 6).
9. Level the laser unit and mark beam position (c).
10. The distance between marks (a) and (c) is the error:
Distance Between Walls
25' (7.7m)
50' (15.4m)
75' (23m)
100' (30.8m)
CHECKING ACCURACY – PLUMB (FIG. 7)
Checking the plumb accuracy of the laser unit can be done most accurately when there is a
substantial amount of vertical height available, ideally 25' (8m). Use one person on the floor to
position the laser unit and another near a ceiling to mark the dot created by the laser as shown
in Figure 7. It is important to conduct a calibration check using a distance no shorter than the
distance of the applications for which the tool will be used.
1. Start by drawing an X on the floor.
2. Place the laser unit on the floor such that the vertical beam is directly above the X.
3. Center the two active bubble vials (E) to level the unit.
4. Mark the center (F) of the dot on the ceiling created by the plumb beam.
5. Turn the unit 180° and position it again above the X mark.
6. Level the laser unit.
7. Mark the center (G) of the dot on the ceiling created by the plumb beam.
The two marks on the 25' (8m) high ceiling should be no more than 1/2" (12.5mm) apart. If
the vertical distance from floor to ceiling is much less than 25' (8m), then the marks should
be closer. For example, if the height of the ceiling is 12.5', then the marks should be 1/4"
(6.5mm) apart.
Checking Level to Square Beam 90˚ Accuracy (Fig. 8)
Refer to the graphic for the location of the DW099 at each step and for the location of the marks
made at each step. All marks can be made on the floor by placing a target in front of the level
or square beam and transferring the location to the floor.
1. Find a room at least 35' (10m) long. Mark a point (H) on the floor at one end of the room.
2. Set up the laser so that its plumb beam is over point (H). Make sure the level beam points
toward the far end of the room.
3. Mark a point (I) on the floor at the center of the room using a target to transfer the level beam
location to the floor.
4. Mark a point (J) on the far wall or transfer the level beam location to the floor.
5. Move the laser to point (I) and align the level beam to point (J) again.
6. Mark the location of the square beam (K) on the floor.
NOTE: To ensure accuracy, the distances from H to I, I to J, and I to K should be equal.
7. Turn the laser 90° so that the level beam aligns with point K.
8. Mark the location of the square beam (L) on the floor as close as possible to point (H).
9. Measure the distance between points (H) and (L). If the measurement is greater than the
values indicated, the laser is out of squareness.
Distance
between
points H and I
17.5' (5m)
35' (10m)
Troubleshooting
THE LASER DOES NOT TURN ON
• Make sure batteries are installed according to the label in the battery compartment.
• Make sure the batteries are in proper working condition. If in doubt, try installing new
batteries.
• Make sure that the battery contacts are clean and free of rust or corrosion. Be sure to keep
the laser level dry and use only new, high-quality, name brand batteries to reduce the
chance of battery leakage.
• If the laser unit is heated above 120˚F (50˚C), the unit will not turn on. If the laser has been
stored in extremely hot temperatures, allow it to cool. The laser level will not be damaged by
pressing the on/off button before cooling to its proper operating temperature.
Service and Repairs
NOTE: Disassembling the laser level will void all warranties on the product.
To assure product SAFETY and RELIABILITY, repairs, maintenance and adjustment should be
performed by authorized service centers. Service or maintenance performed by unqualified
personnel may result in a risk of injury. To locate your nearest D
1-800-4-D
WALT (1-800-433-9258) or go to http://www.dewalt.com on the Internet.
E
WALT accessories specified
E
WALT Industrial Tool
E
WALT (1-800-433-9258).
E
Allowable Error
5/32" (4mm)
5/16" (8.5mm)
15/32" (12.5 mm)
5/8" (17mm)
The 90° angle between the level
beam and square beam is out of
calibration if the distance between
points H and L is:
3/16" (4.5mm)
3/8" (9mm)
WALT service center call
E
FIG. 1
WALT service
E
FIG. 2
FIG. 3
a
FIG. 4
a
FIG. 5
a
FIG. 6
c
a
FIG. 8
Steps / Étapes /
Step / Étape /
Paso 6
B
D
F
FIG. 7
XX
25'
X
Step / Étape / Paso 9
Pasos 1, 2
Step / Étape / Paso 8
Steps
Étapes
Pasos
3, 5
Step / Étape / Paso 4
A
C
E
G
17.5' (5m)
17.5'
(5m)
Step
Étape
Paso
7
17.5'
(5m)
b
b
b