DIP-SWITCH SETTING
Turn off the power to the unit. This
operation should be carried out in the
installation phase, by suitably trained
and qualified personnel only.
The dip-switches are on the electronic
board.
Position
Functions
Dip 1 (Default OFF)
Check water valve / * Thermostat in centralised network (See table):
OFF
No shut-off valve
ON
Shutoff valve present / * Thermostat in centralised network:
Dip 2 (Default OFF)
Position water temperature probe / * Thermostat in centralised network (See table):
OFF
Water temperature probe downstream from shutoff valve / *Thermostat in centralised network
ON
Water temperature probe upstream from shutoff valve
Dip 3 (Default OFF)
Ventilation control:
OFF
Thermostat-controlled ventilation
ON
Continuous ventilation
Dip 4 (Default OFF)
Ventilation enabling:
OFF
Enabling normal band
ON
Enabling reduced band
Dip 5 (Default OFF)
Machine with two or four pipes
OFF
2-pipe fan coils
ON
4-pipe fan coils
Dip 6 (Default OFF)
the presence of the accessory
OFF
Resistance to integration is not present
ON
Presence of resistance to integration
Dip 7 (Default OFF)
Dead band
OFF
Dead band 5° C
ON
Dead band 2° C
Dip 8 (Default OFF)
Minimum speed:
OFF
Inverter minimum speed 55 %, continuous minimum speed 34% (FCLI 8X/12x)
ON
Inverter minimum speed 40 %, continuous minimum speed 25% (FCLI 3X/4x/6x)
SOME EXAMPLES:
ON
1 2 3 4 5 6 7 8
SW
VMF_E18 (default)
ON
1 2 3 4 5 6 7 8
SW
* Centralised control enabled
36
AGLLI10/20NFJ 07/11_4528572_00
**Warning: if the thermostats are
inserted in systems with Centralised
Control or Supervisor (e.g. VMF-E5),
it is necessary to set: Dip1=ON and
Dip2=OFF. The setting takes priority
over the presence of the valve and the
They can be used to obtain the following functions:
ON
ON
OFF
1 2 3 4 5 6 7 8
* With shutoff valve
ON
ON
OFF
1 2 3 4 5 6 7 8
FCXI 20 / 30 / 40
position of the probe.
ON
OFF
SW
* Water probe upstream from the valve
ON
OFF
SW
ON
1 2 3 4 5 6 7 8
SW
ON
1 2 3 4 5 6 7 8
SW
FCXI 50 / 80
ON
OFF
ON
OFF