EXTERNAL CONTACT LOGIC
The thermostat also includes an external
contact that allows to set it to OFF if it
is closed (except if the thermostat is in
anti-freeze mode or as a slave in the TTL
network). This contact could be useful to
manage inputs such as window contacts,
faulty circulation pump, etc.

SLEEP FUNCTION

The Sleep function in the thermostat is
available if the thermostat is interfaced
with a presence sensor (with normally
open logic) connected to its SP input. In
practice the function consists in chang-
ing the regulation setpoint of the fan coil
if the air-conditioned environment is not
The air side season changeover is inhibited when the SP input is kept closed; this function prevents incorrect status changes
due to the change of the setpoint
COMFORT FUNCTION
The set point of centralized systems in
which there are network connected
fan coils, is decided by a central unit.
The user may have the opportunity to
increase or decrease the setpoint accord-
ing to the table below.
CE input status
Closed
Open
occupied; i.e. decreasing if operating
hot, increasing if operating cold. This
function aims at saving energy. In this
specific case, if the thermostat card was
connected to a presence sensor, the logic
of the SP input occurs as follows:
Heating
SP input
Dip 7 Off

Open
°C
Closed
Dead band [°C]
2
5
Machine status
OFF
ON
Cooling
Dip 7 On
Dip 7 Off


°C
°C
Deviation of the setpoint [°C]
+/- 3
+/- 6
AGLLI10/20NFJ 07/11_4528572_00
Dip 7 On

°C
35