DESCRIPTION
The 16E09-101 is a single stage electronic temperature con-
trol, with a Nema 1 rated enclosure, and can be used for most
applications within the temperature control range of -40° to
220°F, (-40° to 104°C). The control has an SPDT (Single Pole
Double Throw) output load relay.
The control has user options to control differential, anti-short
cycle delay, set back, offset, alarms and more. It includes an
NTC (Negative Temperature Coefficient) thermistor tempera-
ture sensor, and can be used with certain other NTC or PTC
(Positive Temperature Coefficient) thermistors that meet the
specified resistance vs. temperature specifications. See the
tables on page 7.
The control can fit many applications, which range from
refrigeration to heating due to the wide temperature range of
the control stated above. Typical applications include walk-
in freezers, beverage coolers, supermarket display cases
for flowers, produce, meats, convenience store refrigerated
cases, food warmers, boiler control, and certain industrial
applications.

PRECAUTIONS

Failure to read and follow all instructions carefully before
installing or operating this control could cause personal
injury and/or property damage.
To prevent electrical shock, personal injury and/or
equipment damage, disconnect electric power to system
at main fuse or circuit breaker box prior to installation
or service.
CONTENTS
Basic Description ........................................................ 1
Precautions ................................................................. 1
Installation ................................................................... 2
Wiring .......................................................................... 3
User Menu .................................................................. 4
Operation .................................................................... 5
Specifications .............................................................. 7
Troubleshooting ........................................................... 8
Save these instructions for future use!
WARNING
!
www.white-rodgers.com
www.emerson.com
16E09-101
Universal Electronic Temperature Control
INSTALLATION AND
OPERATION INSTRUCTIONS
To prevent scald injury, do not use this control to
heat water for bathing, washing, hot tub or similar
applications.
Where failure of this control may result in personal
injury and/or property damage, additional alarms or limit
controls must be installed.
This control is a temperature control and is not to be
used as a temperature limit control.
16E09-101 Optional Accessories / Service Items:
Immerson Well .................................................... F89-0286
Replacement 7.5' NTC Remote Sensor .............. F136-0114
Well Heat Transfer Compound ............................. F145-0163
PART NO. 37-6857G
Replaces 37-6857F
1016
Tabla de contenido
loading

Resumen de contenidos para Emerson 16E09-101

  • Página 1: Tabla De Contenido

    OPERATION INSTRUCTIONS Save these instructions for future use! DESCRIPTION The 16E09-101 is a single stage electronic temperature con- trol, with a Nema 1 rated enclosure, and can be used for most applications within the temperature control range of -40° to 220°F, (-40°...
  • Página 2: Installation

    INSTALLATION To prevent electrical shock and/or equipment dam- The control has a user selection for changing the setpoint to age, disconnect electric power to system at main be either the Cut In or the Cut Out setting. The user must be fuse or circuit breaker box prior to installation or careful to understand how this effects the “range”...
  • Página 3: Wiring

    WIRING Wiring Instruction Notes Fig. 3 Line Voltage Application (Power Stealing) Switch Settings Alarm Output For optional connection Switch SW2 must be set for applications as shown: to customer alarm equipment PTC* (See "Special Note" Temperature in "Operation Section" Sensor for Alarm) Line Voltage (Power Stealing) Line Voltage (Non Power Stealing)
  • Página 4: User Menu

    USER MENU USER MENU OPERATION SETTINGS: Each press of results in forward movement to the next The control has user Menu settings that will determine how Menu item. If you need to change an item “passed”, you the control operates. The unit is shipped with factory de- must repeatedly press , return to the operating mode, fault settings.
  • Página 5: Operation

    USER MENU Options Menu Factory Press Item Description Default to select Comments Binary Input On or Off The default setting of Off will have no affect on the operation of the thermostat. When set to On, it allows an external binary input (switch or relay) to start a tem- perature set back.
  • Página 6 OPERATION Lock Panel (LP) Temperature out of range – If the temperature is more than 5° from the setpoint, continuously for the length of time set in The keypad can be locked to prevent unwanted tampering AL, the alarm relay output will close. The delay should be set with the control settings.
  • Página 7: Specifications

    SPECIFICATIONS Operating Ambient Ratings (Control Enclosure): Load Output Relay: Ratings (Maximum): Operating Temperature: -29°F to 140°F (-34° to 60°C) 120VAC 208VAC 240VAC Full Load Amps NC & Load 16 A 9.2 A Storage Shipping Ambient Ratings: Locked Rotor Amps NC & Load 96 A 55.2 A 48 A...
  • Página 8: Troubleshooting

    Power Stealing line voltage schematic and connect/add a neutral line connection). TECH SUPPORT HELP LINE: 1-888-725-9797 White-Rodgers is a division of Emerson Electric Co. The Emerson logo is a www.white-rodgers.com trademark and service mark www. emerson.com of Emerson Electric Co.